Operating instructions
Fault
code in
the dis-
play
Const. Weath.-
comp.
System char-
acteristics
Cause Remedy
b4 X X Controls as if
the outside
temperature
was 0 °C
Internal fault Replace control
unit
b5 X X Control opera-
tion as per the
delivered con-
dition
Internal fault Replace control
unit
b7 X X Burner
blocked
Boiler codi ng
card fault
Plug in boiler c od-
ingcardorre-
place, if faulty
b8 X X Burner
blocked
Flue gas
temperature
sensor break
Check flue gas
temperature sen-
sor
bA X Mixer "Close" Communica-
tion fault –
extension kit
for heating
circuit M2
Check the exten-
sion kit connec-
tions and coding;
start the ex ten-
sion kit
bC X Control mode
without remote
control
Communica-
tion fault -
Vitotrol re-
mote control,
heating cir-
cuit A1
Check connec-
tions, cable/lead
and coding ad-
dress "A0"
bd X Control mode
without remote
control
Communica-
tion fault -
Vitotrol re-
mote control,
heating cir-
cuit M2
Check connec-
tions, cable/lead
and coding ad-
dress "A0"
bE X Control mode Vitotrol re-
mote control
incorrectly
encoded
Check remote
control DIP switch
setting (see
page 105)
bF X Con trol mode Incorrect
LON com-
munication
module
Replace the LON
communication
module
Fault codes (cont.)
74
Troubleshooting
5692 619 GB