Operating instructions

Fault
code in
the dis-
play
Const. Weath.-
comp.
System char-
acteristics
Cause Remedy
C2 X X Control mode Communica-
tion fault -
solar control
unit
Check the con-
nections and set-
tings of coding
address "54"
C5 X X Control mode,
max. pump
speed
Communica-
tion error
variable
speed inter-
nal pump
Check the coding
address "30" set-
tings; check the
DIP switch set-
tings in the pump
wiring chamber:
Switch 1: OFF,
Switch 2: ON
C6 X Control mode,
max. pump
speed
Communica-
tion fault -
external vari-
able speed
heating cir-
cuit pump,
heating
circuit M2
Check the coding
address "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring chamber:
Switch 1: OFF,
Switch 2: ON
C7 X X Control mode,
max. pump
speed
Communica-
tion fault -
external vari-
able speed
heating cir-
cuit pump,
heating
circuit A1
Check the coding
address "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring chamber:
Switch 1: ON,
Switch 2: OFF
Cd X X Control mode Communica-
tion fault
Vito com 100
(KM BUS)
Check connec-
tions, Vitocom 100
and coding ad-
dress "95"
CE X X Control mode Communica-
tion fault
ext. exten-
sion
Check connec-
tions and coding
address "2E"
Fault codes (cont.)
75
Troubleshooting
5692 619 GB