Operating instructions

Fault
code in
the dis-
play
Const. Weath.-
comp.
System char-
acteristics
Cause Remedy
CF X C ontrol mode Commun ica-
tion fault -
LON com-
munication
module
Replace the LON
communication
module
dA X Control mode
without room
influence
Room tem-
perature
sensor, heat-
ing circuit A1
shorted out
Check the room
temperature sen-
sor heating cir-
cuit A1
db X Control mode
without room
influence
Room tem-
perature
sensor, heat-
ing circuit
M2 shorted
out
Check the room
temperature sen-
sor heating cir-
cuit M2
dd X Control mode
without room
influence
Room tem-
perature
sensor, heat-
ing circuit A1
lead broken
Check the room
temperature sen-
sor, heating ci r-
cuit A1 and t he
remote control
DIP switch setting
(see page 105)
dE X Control mode
without room
influence
Room tem-
perature
sensor, heat-
ing circuit
M2 lead bro-
ken
Check the room
temperature sen-
sor, heating ci r-
cuit M2 and the
remote control
DIP switch setting
(see page 105)
E4 X X Burner
blocked
Fault sup-
ply voltage
24 V
Replace control
unit
E5 X X Burner
blocked
Flame amp li-
fier fault
Replace the con-
trol unit.
Fault codes (cont.)
76
Troubleshooting
5692 619 GB