Operating instructions

1. Pull th e leads off the temperatu re
limiter.
2. Check the continuity of the tem-
perature limiter with a multimeter.
3. Remove the faulty temperature lim-
iter.
4. Coat the replacement temperature
limiter with heat conducting paste
and install.
5. After commissioning, press reset
button "E" on the control uni t.
Checking and replacing the differential pressure sensor
In case of fault m essages concerning the differential pressure sensor, check the
sensor for:
&
Correct installation
&
Electrical connectio n
&
Correct position of th e O-rings inside the a daptor
&
Plugs in te st nipple s
Replace the sen sor if fault message s persist.
Repairs (cont.)
85
Troubleshooting
5692 619 GB