Operating instructions

Rated voltage: 230 V~
Ratedfrequency: 50Hz
Rated current : 6.3 A~
Safety class: I
Protection level : IP X 4 D to
EN 60529
Permissible ambient temperature
&
in operat ion: 0 to +40 °C
&
during storage
and transport:
-20to+6C
Electronic temp era-
ture limiter setting:
82 °C
Temperatur e limiter
setting:
100 °C (fixed)
Mains fuse: Max. 16 A
Power consumption
&
Circulation pump: Max. 115 W
&
Burner: Max. 60 W
&
Control unit: Max. 10 VA
Gas fired boiler, category II
2ELL3P
Rated output TV/TR 50/30 °C kW 6.6 to 26
Rated output range kW 6.3to24.7
Connect ion valu es
*
1
Relative to the max. load
with with H
uB
natural gas E 9.45 kWh/m
3
34.02 MJ/m
3
m
3
/h 2.65
natural gas LL 8.13 kWh/m
3
29.25 MJ/m
3
m
3
/h 3.08
LPG 12.79 kWh/m
3
46.04 MJ/m
3
m
3
/h 1.94
Product ID _-0085 BO
0338
Product characteristics (to EnEV [Germany])
Rated output range kW 6.6to26
Efficiency µfor
&
100 % of rated output % 96.3
&
30 % of rated output % 107.4
Standby loss q
B,70
*
2
%0.7
Power consumption
*
2
for
&
100 % of rated output W 207
&
30 % of rated output W 69
Specification
126
Specification
5692 548 GB
*1
The supply values are only for reference (e.g. i n the gas contract application) or to esti-
mate the supplementary volumetric settings. Because of factory settings, the gas pres-
sure m ust not be altered from these values. Reference: 15 °C, 101 3 mbar.
*2
Max. limit to EnEV