Operating instructions

5. Record the gas type in the commis-
sioning/service report on p age
120.
Checking static and supply pressure
Danger
Higher CO emis sions can le ad to poisoni ng.
Measure the CO va lue before and a fter any work on gas equ ipment to
prevent any h ealth hazards and to e nsure the per fect operatio nal condi-
tion of the system.
Operation with LPG
Flush the LPG tank twi ce during commissionin g/replacement. Tho roughly vent
the tank and gas lin es after flushin g.
1. Close the gas shut-off v alve.
2. Releas e the screw insi de test nip-
ple PE A on the gas combination
valve, but do n ot remove, and con -
nect the pressure gauge.
3. Open the gas shut-off valve.
4. Check the static pressure; it should
be a max. of 57.5 mbar. Record the
actual value in the service report.
5. Start up boiler.
Note
During commis sioning, the boi ler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 seconds, press E to
reset the burner.
Further details regarding the individual steps (cont.)
13
Initial start-up, inspection, maintenance
5692 548 GB