Operating instructions
Checking the CO2 settings
Vitodens 333 is set up in the factory for natural gas E, and can be converted to
natural gas LL or LPG P using a conversion kit.
During commissioning o r maintenance, check the CO
2 level at the boiler adap-
tor.
Note
The MatriX burne r for Vitodens 333 is pr eset for the entire ga s group. Therefo re,
the burner requires no further setting or adjustment.
Subject to the Wobbe index, the CO
2 content fluctuates between
&
6.6 to 10.0 % for natural gas E
&
7.0 to 10.0 % for natural gas LL and
&
8.5to10.5%forLPGP.
Compare the actual CO
2 value with the above CO2 value range s for the indiv i-
dual gas groups (check the gas group with your mains gas or LPG supplier).
If the actual CO
2 valu e deviates by mor e than 1 % for natura l gas or 0.5 % for
LPG, proceed as f ollows:
&
Check whether the correct gas restrictor has been installed.
&
Check the balanced flue system for soundness, see page 18.
Further details regarding the individual steps (cont.)