Operating instructions
7. Check the CO2 content. Should the
actual value deviate by more than
1 % from the above range, imple-
ment steps from p age 15 (possib ly
replace the burn er).
8. After testing, press d.
9. Enter actual values into the service
report.
Setting the max. output
Note
The max. output ca n be limited for heating operation. You can limit the output
via the modulation range. The control pressure acts as standard value for set-
ting the required output.
1. Start up boiler.
2. Press both K and F simulta-
neously until 100 flashes on the
display, (equals 100 % of the rated
output) and A appears. On
weather-compensated control
units, the display additionally
shows Max. output.
3. With a/b select the required
value in % of rated o utput as max.
output.
4. Confirm the set value with d .
5. Record the settings for max. outp ut
on the additional type plate
included with the technical docu-
mentation. Affix the type plate next
to the original type plate on top of
the boiler.
Further details regarding the individual steps (cont.)
17
Initial start-up, inspection, maintenance
5692 548 GB