Operating instructions

Coding in
the as
delivered
condition
Address:
value
Function mode Coding
change
Address:
value
Possible change
59:0 DHW cylinder loading:
Starting point -2 .5 K
Stoppin g point +2. 5 K
59:1
to
59:10
Starting point ad justable
from1to10Kbelowthe
set value
60:10 During DHW loading,
the boiler water tem-
perature is a m aximum
of 20 K highe r than the
set DHW temperature
60:5
to
60:25
Thedifferencebetween
the boiler water tempera-
ture and the set DHW
temperature is adjustable
from 10 to 50 K
62:2 Circulation pump with 2
minutes run-on time
62:0 Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from1to15minutes
63:0
*
1
Without auxilia ry func-
tion for DHW loading
63:1 Additional function: 1 x
daily
63:2
to
63:14
Every 2 to every 14 da ys
63:15 2 x daily
65:... Information regarding
the type of diverter
valve (not adjustable)
65:0 Without diverter valve
65:1 Diverter valve b y Viess-
mann
65:2 Diverter valve by Wilo
65:3 Diverter valve by Grund-
fos
6C:100 Set speed internal DHW
loading pump 100 %
6C:0
to
6C:100
Set speed adjustable
from0to100%
6F:100 Max. output during
DHW loading 100 %,
defaulted by the boiler
coding card
6F:0
to
6F:100
Max. output during DHW
loading adjustable from 0
to 100 %
Code 2 (cont.)
48
Coding
5692 548 GB
*1
Only for constant temperature control units.