Operating instructions
Coding in
the as
delivered
condition
Address:
value
Function mode Coding
change
Address:
value
Possible change
A3:2 Outside temperature
below 1 °C: Heati ng cir-
cuit pump ON
Outside temperature
above 3 °C: Heating cir-
cuit pump OFF
Note
When selecting a value
below 1 °C there will be
a risk of pipes outside
the thermal insulation
envelope of the house
freezing-up. The
standby mode, i n parti-
cular, should be
observed,e.g.during
holidays.
A3:-9
to
A3:15
Heating circuit pump ON/
OFF (see the following
table)
Parameters Heating circuit pump
Address A3:... ON at OFF at
-9 -10 °C -8 °C
-8 -9 °C -7 °C
-7 -8 °C -6 °C
-6 -7 °C -5 °C
-5 -6 °C -4 °C
-4 -5 °C -3 °C
-3 -4 °C -2 °C
-2 -3 °C -1 °C
-1 -2 °C 0 °C
0-1°C1°C
10°C 2°C
2
to
1°C
to
3°C
15 14 °C 16 °C
Code 2 (cont.)
53
Coding