Operating instructions
Coding in
the as
delivered
condition
Address:
value
Function mode Coding
change
Address:
value
Possible change
b0:0
*
1
With remote control:
Heating mode/r educed
mode: Weather-com-
pensated
*
2
b0:1 Heating mode: Weather-
compensated
Reduced mode: With
room temperature hook-
up
b0:2 Heating mode: With room
temperature hook-up
Reduced mode: Weathe r-
compensated
b0:3 Heating mode/reduced
mode: With room tem-
perature hook -up
b2:8 With remote control unit
andfortheheatingcir-
cuit, heating with room
temperature hook-up
must be encoded:
Room influence factor
8
*
2
b2:0 Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
b5:0
*
1
With remote control:
Without room tempera-
ture-dependent heating
circuit pump logic func-
tion
*
2
b5:1
to
b5:8
Heating circuit pump
logic function - see the
following table
Parameter
address b5:...
With heating circuit pump logic function: Heating cir-
cuit pump OFF, if
1: active RT
Actual >RTSet +5K;passiveRTActual <RTSet +4K
2: active RT
Actual >RTSet +4K;passiveRTActual <RTSet +3K
3: active RT
Actual >RTSet +3K;passiveRTActual <RTSet +2K
4: active RT
Actual >RTSet +2K;passiveRTActual <RTSet +1K
5: active RT
Actual >RTSet +1K;passiveRTActual <RTSet
6: active RTActual >RTSet;passiveRTActual <RTSet -1K
Code 2 (cont.)
57
Coding
5692 548 GB
*1
Only for weather-compensated control unit.
*2
Change the coding for the heating circuit without mixer A1 or for mixer circuit M2 , if the
remote control unit affects that heating circui t.