Operating instructions
Parameter
address b5:...
With heating circuit pump logic function: Heating cir-
cuit pump OFF, if
7: active RT
Actual >RTSet -1K;passiveRTActual <RTSet -2K
8: active RT
Actual >RTSet -2K;passiveRTActual <RTSet -3K
Coding in
the as
delivered
condition
Address:
value
Function mode Coding
change
Address:
value
Possible change
Boiler circuit, mixer circuit
C5:20
*
1
Electronic mi nimum
flow temperature limit in
standard mode 20 °C
C5:1
to
C5:127
Minimum temperature
limit in standard mode
adjustable from 1 to
127 °C
C6:74
*
1
Electronic max imum
flow temperature limit
74 °C
C6:0
to
C6:127
Maximum limit adjustable
from1to127°C
d3:14
*
1
Heating curve slope =
1.4
d3:2
to
d3:35
Heating curve sl ope
adjustable from 0.2 to 3.5
(see page 34)
d4:0
*
1
Heating curve level =
0
d4:–13
to
d4:40
Heating curve level
adjustable from – 13 to 40
(see page 34)
d5:0
*
1
The external operat-
ing mode changeover
changes the h eating
program to "Consta nt
operation w ith reduced
room temperatur e"
d5:1 The exte rnal operating
mode changeover
changes the hea ting pro-
gram to "Constant o pera-
tion with standard room
temperature"
E1:1
*
1
With remote control:
Set day value is adjus-
table at the remote con-
trol unit from 10 to
30 °C
E1:0 Set day value adjustable
from3to23°C
E1:2 Set day value adjustable
from 17 to 37 °C
E2:50
*
1
With remote control
unit and for the heating
circuit, heatin g with
room temperature hook-
up must be enco ded:
E2:0
to
E2:49
Display correction – 5K
or
Display correction – 0.1 K
E2:51
to
Display correction +0.1 K
or
Code 2 (cont.)
58
Coding
5692 548 GB
*1
Only for weather-compensated control unit.