Operating instructions
Coding in
the as
delivered
condition
Address:
value
Function mode Coding
change
Address:
value
Possible change
No display correction of
the actual room tem-
perature
E2:99 Display correc tion +4.9 K
E5:0
*
2
Without variable
speed circuit pump
E5:1 With variable speed cir-
cuit pump; automatic
recognition
E6:65
*
2
Max. speed of the
variable speed pump =
65 % of max. sp eed in
standard mode
E6:0
to
E6:100
Maximum speed adjusta-
blefrom0to100%of
max. speed
E7:30
*
2
Min. speed of the vari-
able speed pu mp = 30
%ofmax.speed
E7:0
to
E7:100
Minimum speed adjusta-
blefrom0to100%of
max. speed
E8:1
*
2
Min. speed subject to
the setting in coding
address "E9 "
E8:0 Speed subject to the set-
ting in coding address
"E7"
E9:45
*
2
Speed of the variable
speedpump=45%of
max. speed in reduced
mode
E9:0
to
E9:100
Speed adjustable from 0
to 100 % of max. speed
Mixer circuit
F1:0 Screed function inactive
(only for weather-co m-
pensated control units)
F1:1
to
F1:5
Screed drying function
adjustab le in accordan ce
with five optional tem-
perature time profiles
(see page 105)
Note
Observe the screed dry-
ing supplier's instruc-
tions.
Observe DIN 4725-2 or
local regulations. The
report to be provided by
the heating contractor
Code 2 (cont.)
59
Coding
5692 548 GB
*2
Only for weather-compensated control unit.