Operating instructions

Coding in
the as
delivered
condition
Address:
value
Function mode Coding
change
Address:
value
Possible change
20 minutes
F6:0
*
6
*
6
In the "DHW only"
operating mode , the
internal circulation
pump is permanen tly
OFF
F6:1
to
F6:24
In the "DHW only" operat-
ing mode, the i nternal cir -
culation pump will be
started1to24timesper
day for 10 minute s
respectively.
F6:25 In the "DHW only" operat-
ing mode, the i nternal cir -
culation pump is
permanently O N
F7:0
*
6
*
6
Internal circulation
pump is permanen tly
OFF in operating mode
"Standby mode"
F7:1
to
F7:24
In "Standby mode", the
internal circulation pump
willbestarted1to24
times per day for
10 minutes re spectivel y.
F7:25
*
6
*
6
Internal circulation
pump is permanen tly ON
in operatin g mode
"Standby mode"
Resetting the coding to the as delivered condition
1. Press L and G simultan eously
for approx. 2 secon ds.
2. Press e.
"Basic setting? Yes" wit h d.
With a or b, you can select
"Basic setting? Yes " or "Basic set-
ting? No".
Code 2 (cont.)
61
Coding
5692 548 GB
*6
Only for constant temperature control units.