Operating instructions
Display screen
Brief scan
d Variabl e
speed
pump
0: excl.
1: Wilo
2: Grund-
fos
Software
version
variable
speed pump
Testing outputs (relay test)
Weather-compensated control unit
1. Press K and d simultaneously
for approx. 2 secon ds.
Relaytestisactivated.
2. Select the relay outputs with a
and b.
3. Press d.
Relay test is co mpleted.
Subject to the actual equipment level, the following relay outputs can be con-
trolled:
Display Explanations
Basic load Burner mod ulation low er output
Full load Burner modulation upper output
Heating valve Diverter valve set to heating mode
Valve central pos. Changeover valve in central position (fill)
DHW valve Diverter valve set to DHW mode
Int. pump ON Int. pump/output 20 ON
Close mixer M ixer extension
Open mixer Mixer exten sion
Heating circ. pump M2 ON Mixer extension
Output int. Internal extension
Heating circ. pump A1 ON Ext. extension
Cylinder loading pump ON Ext. extension
DHW circ. pump ON Ext. extension
Central fault display ON Ext. extension