Operating instructions
Fault code
in the dis-
play
Const. Weat-
h.
comp.
System
character-
istics
Cause Remedy
9C X X Cylinder tempera-
ture sensor lead
break
9F X X Control
mode
Solar control un it
error message
See solar
control unit
service
instructions
A7 X Control
mode
Faulty operating
interface
Replace
operating
interface
b0 X X Burner
blocked
Flue gas tempera-
ture sensor shor t
circuit
Check the
flue gas tem-
perature sen-
sor (see
page 87)
b8 X X Flue gas tempera-
ture sensor brea k
b1 X X Control
mode
Communication
fault – program-
ming unit ( internal)
Check con-
nections and
replace the
programming
unit, if neces-
sary
b4 X X Emissions
test mode
Internal error ana-
log converter
Replace con-
trol unit
b5 X X Control
mode
Internal error Replace con-
trol unit
b7 X X Burner
blocked
Boiler coding card
missing, faulty or
incorrect card
inserted
Plug in the
boiler coding
card or
replace, if
faulty
bA X Mixer M2
continues
to move
Communication
fault - extension kit
for mixer circui t M2
Check the
extension kit
connections
and coding.
Start the
extension kit.
Checking and acknowledging faults (cont.)
77
Troubleshooting
5692 548 GB