Operating instructions
Fault code
in the dis-
play
Const. Weat-
h.
comp.
System
character-
istics
Cause Remedy
bC X Control
mode with-
out remote
control
Communication
fault - Vitotrol
remote control
heating circuit A1
Check con-
nections,
cable, coding
address A0
and the
remote con-
trol DIP
switches
bd X Control
mode with-
out remote
control
Communication
fault - Vitotrol
remote control
heating circuit M2
bE X Control
mode
Vitotrol remote
control incorrectly
encoded
Check the
DIP switch
settings of
the remote
control
bF X Control
mode
Incorrect LON com-
munication mod ule
Replace the
LON commu-
nication mod-
ule
C2 X X Control
mode
Communication
fault - solar contro l
unit
Check con-
nections and
coding
address 54.
C5 X X Control
mode,
max. pump
speed
Communication
error - variable
speed internal
pump
Check coding
address 30
settings;
check the
heating cir-
cuit pump
DIP switch
settings.
Checking and acknowledging faults (cont.)
78
Troubleshooting
5692 548 GB