Operating instructions
Fault code
in the dis-
play
Const. Weat-
h.
comp.
System
character-
istics
Cause Remedy
C6 X Control
mode,
max. pump
speed
Communication
fault - variable
speed heating ci r-
cuit pump, heating
circuit M2
Check coding
address E5
settings;
check the
heating cir-
cuit pump
DIP switch
settings
C7 X X Control
mode,
max. pump
speed
Communication
fault - variable
speed heating ci r-
cuit pump, heating
circuit A1
Check coding
address E5
settings;
check the
heating cir-
cuit pump
DIP switch
settings
Cd X X Control
mode
Communication
fault Vitocom 100
(KM BUS)
Check the
Vito com 100
and connec-
tions
CE X X Control
mode
Communication
error - ext. exten-
sion
Check con-
nections and
coding
address 2E
settings.
CF X Control
mode
Communications
fault - LON commu -
nication module
Replace the
LON commu-
nication mod-
ule
dA X Control
mode with-
out room
influence
Room temperature
sensor hea ting cir-
cuit A1 shorted out
Check the
room tem-
perature sen-
sor - heating
circuit A1
db X Heating circuit M2
room temperature
sensor shor ted out
Check the
room tem-
perature sen-
sor - heating
circuit M2
Checking and acknowledging faults (cont.)
79
Troubleshooting
5692 548 GB