Technical data

29
20. Depress the Set button. The value that appears is the factory or previously
set value. Depress the Set button and hold until the value changes (5
seconds). Set the value to minimum system pressure that is desired.
21. Depress the Mode/Enter button to return to rP1.
22. Depress the Mode/Enter button to change the display value to OU1.
23. Depress the Set button. The value that appears is the factory or previously
set value. Depress the Set button and hold until the value changes (5
seconds). Set the value to Hno
.
24. Depress the Mode/Enter button to return to OU1.
25. Wait (15 seconds) and the switch will return to normal operation mode.
26. The switch is now properly set for operation.
27. Other values that may be set or reviewed.
a. H1 and LO can be set at desired value.
b. COF should only be adjusted if the pressure reading is absolutely
determined to be inaccurate.
c. CAr should only be used if there is a value in COF.
6.5 DAP should always be set at 0 to ensure that the system shuts down
the solenoid as soon as the pressure is obtained.
DiS should be set at d1, d2, or d3.
7.0 CS-1 ANTIFREEZE PUMP SYSTEM
ISOLATION VALVE
SYSTEM(S)
CONNECTION(S)
PUMP
65 OR 160
CONTROL
PANEL
LIQUID SUPPLY
GALLON TANK
7.1 Description
The Viking CS-1 Tank and Pump Package is an integrated storage tank and
pumping system designed for use with the Viking ESFR Cold Storage System.
This is a Pre-Primed Single Interlocked Preaction System providing fixed fire
protection for refrigerated or cold warehouse storage and is also appropriate for
unheated storage applications in areas subject to freezing, to a minimum
temperature of -21 °F (-29.4 °C).
This is a pre-primed preaction system with electric release that utilizes a deluge
valve with conventional and electric release trims. The riser consists of two
Viking Easy Riser
TM
Swing Check Valves, one with special cold trim and the
second with by-pass trim to isolate the antifreeze in the system from the water