Technical data

45
12.3 Features
Has a freeze temperature rating (freeze point) of -26 °F (-32.2 °C). (Note:
Freeze temperature is where ice crystals begin to form.)
Is a ready-to-use solution pre-mixed in the proper 50% propylene glycol
concentration for the Viking ESFR Cold Storage System, in areas subject to
freezing, to a minimum temperature of -21 °F (-29.4 °C).
Was utilized in the full-scale research fire tests for the Viking ESFR Cold
Storage System.
Includes corrosion inhibitors to provide corrosion control and microbiological
control of the system piping and components.
13.0 ANTIFREEZE SOLUTION 35%
13.1 Description
Viking Firefighter Eliminator C is a certified premixed 35% propylene glycol and
water antifreeze solution required for use with the Viking ESFR Cold Storage
System for use in applications having a minimum temperature as low as 8 °F (-
13.3 °C). The piping system is filled with pressurized propylene glycol and water
solution maintained from a pressure pump system that controls and maintains
the desired solution pressure. This is a pre-primed preaction system with electric
release that utilizes a deluge valve with conventional and electric release trims.
The riser consists of two Viking Easy Riser
TM
Swing Check Valves, one with
special cold trim and the second with by-pass trim to isolate the antifreeze in the
system from the water supply.
13.2 Typical Properties
Concentration
35% by volume propylene glycol
plus <5% dipotassium phosphate (corrosion inhibitor)
plus <3% coloring
plus remainder - deionized water
Specific Gravity
1.033 @ 68 °F (20 °C)
1.040 @ 8 °F (-13.3 °C)
Density
64.46 lbs./cu ft @ 68 °F (20 °C)
64.90 lbs./cu ft @ 6 °F (-14.5 °C)
Viscosity
4 CPS @ 68 °F (20 °C)
18 CPS @ 6 °F (-14.5 °C)
Minimum use temperature: 8 °F (-13.3 °C)
Freeze point: 2.4 °F (-16.4 °C)
pH: 9