Technical data
45
12.3 Features
• Has a freeze temperature rating (freeze point) of -26 °F (-32.2 °C). (Note:
Freeze temperature is where ice crystals begin to form.)
• Is a ready-to-use solution pre-mixed in the proper 50% propylene glycol
concentration for the Viking ESFR Cold Storage System, in areas subject to
freezing, to a minimum temperature of -21 °F (-29.4 °C).
• Was utilized in the full-scale research fire tests for the Viking ESFR Cold
Storage System.
• Includes corrosion inhibitors to provide corrosion control and microbiological
control of the system piping and components.
13.0 ANTIFREEZE SOLUTION 35%
13.1 Description
Viking Firefighter Eliminator C is a certified premixed 35% propylene glycol and
water antifreeze solution required for use with the Viking ESFR Cold Storage
System for use in applications having a minimum temperature as low as 8 °F (-
13.3 °C). The piping system is filled with pressurized propylene glycol and water
solution maintained from a pressure pump system that controls and maintains
the desired solution pressure. This is a pre-primed preaction system with electric
release that utilizes a deluge valve with conventional and electric release trims.
The riser consists of two Viking Easy Riser
TM
Swing Check Valves, one with
special cold trim and the second with by-pass trim to isolate the antifreeze in the
system from the water supply.
13.2 Typical Properties
Concentration
35% by volume propylene glycol
plus <5% dipotassium phosphate (corrosion inhibitor)
plus <3% coloring
plus remainder - deionized water
Specific Gravity
1.033 @ 68 °F (20 °C)
1.040 @ 8 °F (-13.3 °C)
Density
64.46 lbs./cu ft @ 68 °F (20 °C)
64.90 lbs./cu ft @ 6 °F (-14.5 °C)
Viscosity
4 CPS @ 68 °F (20 °C)
18 CPS @ 6 °F (-14.5 °C)
Minimum use temperature: 8 °F (-13.3 °C)
Freeze point: 2.4 °F (-16.4 °C)
pH: 9