Technical data

Page 56
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
ESFR PRE-PRIMED SINGLE
INTERLOCK PREACTION
COLD STORAGE SYSTEM
March 7, 2008
12. Fire ghter Eliminator
A. Description
Viking Firefighter Eliminator C and F is a certified premixed propylene glycol/water antifreeze
solution required for use with the Viking ESFR Cold Storage System.
B. Technical Data
C. Inspections, Tests and Maintenance
Field mixing of propylene glycol and site water is strictly prohibited, as the control of the mixture
cannot be assured. Improper field mixing of solution can result in reduced capability to prevent
freezing or to control a fire. Firefighter Eliminator is already premixed and ready to use.
Testing the Solution:
Antifreeze solution shall be checked semi-annually with a refractometer to detect the concen-
tration of antifreeze solution and effectiveness against freezing. Sampling shall be taken from
multiple points within the freezer system (refer to the instructions on data page 45d for fluid
sampling). When draining sample antifreeze solution from the system, be sure to shut off the
system control valve directly upstream of the Easy Riser
®
Check valve so that water doesn’t
enter the system.
Table 17 - Typical Properties (Not for specification purposes)
Concentration Part Numbers Minimum use
Temperature
Freeze
Point
pH Apperance
Firefighter C 35% by volume propylene glycol
< 5% dipotassium phosphate
< 3% coloring
12968-55 = 55 gallon drum
12968-275 = 275 gallon drum
12968-BULK = tanker delivery
8 °F
(-13.3 °C)
2.4°F
(-16.4 °C)
9 Fluorescent
green color
Firefighter F 50% by volume propylene glycol
< 5% dipotassium phosphate
< 3% coloring
12967-55 = 55 gallon drum
12967-275 = 275 gallon drum
12967-BULK = tanker delivery
-21 °F
(-29.4 °C)
-26 °F
(-32.2 °C)
9 Fluorescent
orange color
For further details, see the Viking Firefighter Eliminator C Material Safety Data Sheet (pages 49e-g and 50e-g).
Environmental & Toxicological Information: Viking Firefighter Eliminator is virtually harmless to animals or plants; however, as with any sub-
stance, care should be taken to prevent discharge from entering ground water, surface water, or storm drains. Disposal of this solution should be
made in accordance with federal, state, and local regulations.
Propylene glycol/water solutions are designed to be installed on systems supplied by potable water supplies. Local authorities should be
consulted prior to draining system to storm sewers or to natural drainage areas.
Manufactured by: The Noble Company, 7300 Enterprise Dr., Spring Lake, MI U.S.A. 49456
Table 19 - Propylene Glycol Refractive Index
Solution Freezing Point
Volume %
Propylene
Glycol
Refractive
Index
71.6 °F (22 °C)
Firefighter 50%
Eliminator F
25.8 °F (-32.1 °C) 48.9% 1.3892
28.3 °F (-33.5 °C) 49.9% 1.3903
-31 °F (-35.0 °C) 50.9% 1.3914
Firefighter 35%
Eliminator C
2.5 °F (-16.4 °C) 34.4% 1.3733
.9 °F (-17.3 °C) 35.5% 1.3744
-.8 °F (.18.2 °C) 36.5% 1.3756
Table 18 - Solution Properties for Given
Temperatures
Solution Temperature Specific
Gravity
Density
(lbs/ft
3
)
Viscosity
(cps)
Firefighter 35%
Eliminator C
6 °F (-14.5 °C) 1.040 64.90 18
68 °F (20 °C) 1.033 64.46 4
Firefighter 50%
Eliminator F
-20° F (-28.9 °C) 1.085 67.70 180
-10 °F (-23.3 °C) 1.061 66.20 96
0 °F (-17.8 °C) 1.056 65.89 61
60 °F (15.6 °C) 1.041 64.96 8.13