Vent-10
Ventilation VIKING 5 SERIES
Hood Data
Model Number CFM Recommended Duct Size Max Duct Run
120 V/60 Hz
Max Amps
FOR USE WITH HOODS
VINV300 (interior) 300 7" round 50 feet (15.2m)
VINV600 (interior) 600 7" round 50 feet (15.2m)
DEV900 (exterior) 900 10" round 50 feet (15.2m)
VINV1200 (interior) 1200 10" round 50 feet (15.2m)
DEV1200 (exterior) 1200 10" round 50 feet (15.2m)
DEV1500 (exterior) 1500 10" round 75 feet (22.9m)
DIL1200 (in-line) 1200 10” round 50 feet (15.2m)
FOR USE WITH VDD 5 SERIES DOWNDRAFTS
VDVI600 (interior) – NEW 600 8" round 40 feet (12.2m) 3.0
VDVE900 (exterior) – NEW 900 10" round 50 feet (15.2m) 5.7
VDVE1200 (exterior) – NEW 1200 10" round 50 feet (15.2m) 6.0
Proper Installation/Ducting Is Extremely Important To Ensure Maximum Performance From Any Ventilation Product
x All CFMs stated based on tests with .1 static pressure: without applying static pressure (some brands consciously do not), CFM could be greatly overstated.
x Duct run length is for general reference only; for longer duct runs, increase duct size and contact a qualified and trained installer.
x Straight runs and gradual turns are best; for example, each 90° elbow is equivalent to 5-10 feet (1.52-3.05cm) of straight run.
x Never use flexible duct; it creates back pressure/air turbulence and greatly reduces performance.
x Proper performance is dependent upon proper ducting; make sure that a qualified and trained installer is used.
x Check with a qualified and trained installer or local codes for makeup air requirements, if any.
x Max. amp rating for hoods includes recommended ventilator kit rating; all products must be hard wired direct with 2-wire with ground
x A 1200 or 1500 CFM (if applicable) ventilator kit, or in-line blower should be used when installed over range/rangetops with gas char-grill.