Installation Instructions

10
Electrical Requirements
Electrical Requirements
This product is manufactured with the neutral terminal connected to the cabinet. Use a 3-wire, agency approved, power supply
kit with closed loop terminals rated per the National Electrical Code, ANSI/NFPA 70-latest edition (See Rating chart below). If local
codes prohibit grounding through the neutral, use a 4-wire, agency approved, power supply kit with closed loop terminals rated
per the National Electrical Code, ANSI/NFPA 70-latest edition (See Rating chart below).
RATING* Specifi ed Rating of Power Supply Cord Kit and Circuit Protection
120/240 Volts 120/208 Volts Amps
4.5 - 10.2 KW 4.5 - 10.2 KW 50
*The National Electric Code calculation for Electrical Load is less than the Total Connected Electrical Load listed on the model/
serial rating plate.
A GFI shall be used if required by NFPA-70 (National Electric Code), federal/state/local laws, or local ordinances.
The required use of a GFI is normally related to the location of a receptacle with respect to any signifi cant sources of water or
moisture.
Manufacturer will NOT warranty any problems resulting from GFI outlets which are not installed properly or do not meet the
requirements below.
If the use of a GFI is required, it should be:
•Of the receptacle type (breaker type or portable type NOT recommended)
•Used with permanent wiring only (temporary or portable wiring NOT recommended)
•On a dedicated circuit (no other receptacles, switches or loads in the circuit)
•Connected to a standard breaker of appropriate size (GFI breaker of the same size NOT recommended)
•Rated for Class A (5 mA +/- 1 mA trip current) as per UL 943 standard
•In good condition and free from any loose-fi tting gaskets
•Protected from moisture (water, steam, high humidity) as much as reasonably possible
WARNING
ELECTRICAL SHOCK HAZARD
To avoid the risk of electrical shock, personal injury or death;
verify electrical power is turned off at the breaker box and gas
supply is turned off until the range is installed and ready to
operate, installation by an authorized installer only.