User manual
• RECEIVER ID
The option has importance when there are more receivers connected to the same
monitoring software. If each receiver has different number, in event list it can be seen
which receiver sent the given event.
• PORT SETTING
You can check the actual serial port settings in this menu. Default values: 9600 (speed),
8, NONE (Data Bits & Parity)
F2 (PORTS) / F3 (TCP/IP)
In this menu you can configure the main monitoring receiver IP parameters and
settings.
Note: After changing all kind of IP parameters please always restart the receiver unit (if
restart doesn't happen automatically. For this exit the menu, then F3 (UTIL) / F3
(RESET) / F3 (RESET).
CONSOLE VER: CPM2.60.BC06
TCP/IP OPTIONS
IP ADDRESS 192 168 001 240
NETMASK 255 255 255 000
GATEWAY 000 000 000 000
RECEIVE PORT 270F (09999)
PROGRAM PORT 0017 (00023)
IP MONITORING OFF TEST FILTER OFF
MONITOR PERIOD 05A0 (01440)
CID TEST EVENT 16A3
WEB HTTP PORT 0050 (00080) LINES 024
WEB PASSWORD NO
+ – PAGE CANCEL
F1 F2 F3 F4
It is recommended to modify the following settings only:
• IP ADDRESS
Here you can define the ENIGMA II unit private (internal) IP address in local area
network. Take care to not use address which is used by another device, or which can be
given by DHCP service.
10