www.winemate.com Wine Cooling System Installation, Use & Care Manual WM-1500CD WM-1500CTED WM-2500CD WM-2500CTED www.vinotemp.
Important Safety Information • • • DO NOT PLUG IN UNTIL 24 HOURS AFTER DELIVERY. DO NOT USE A GROUND FAULT INTERRUPTER (GFI). A DEDICATED 20 AMP CIRCUIT IS REQUIRED.
Table of Contents Features & Specifications…………….………….…………..3 Installation Instructions……………………………………..5 Temperature and Humidity ……………………………..…10 Care Guide………………………………..…………………14 Troubleshooting……………………………………………..15 Wiring Diagram……………………………………….………18 Customer Support……………………………………………20 Warranty……………………………………………………….
Features and Specifications • • • • • • • WM-1500CD, CTED and WM-2500CD, CTED cooling units are designed and used to provide a subtle temperature between 50~65 °F for a properly insulated wine cabinet. The refrigerated space will maintain humidity range within 50~70% RH. These temperature and humidity ranges are optimized for long term storage of wine. Temperature is controlled and humidity is adjusted using patented technology. Bottom cold-air supply is optimized for use in the wine cabinets.
Fig. 1.2 DIMENSIONS (in) The specifications and dimensions are listed as follows: CFM Cabinet Size (cu ft) Electrical Weight(lb) 120 90 115V/60Hz/4A 50 Top Exhaust 120 90 115V/60Hz/4A 50 WM-2500cd Rear Exhaust 180 200 115V/60Hz/5A 55 180 200 115V/60Hz/5A 55 Model Exhaust WM-1500cd Rear Exhaust WM1500cted WM2500cted Top Exhaust NOTES: • Also see the voltage, frequency and current specified on the label at the cooling unit.
Installation Instructions NOTES: • Mounting brackets, screws, gaskets and other seal materials are not included. • Do not install any ducts onto the supply, return, intake and exhaust. • There is a grommet on the power cord and it must be installed properly, otherwise hot air may enter into the cabinet. • We strongly recommend against the use of an extension cord.
Fig. 2.1 CUTOUT AND HOLE DIMENSIONS • • • • The cooling unit produces cooling supplied into the cabinet, meanwhile it also generates heat that must be exhausted outside the cabinet. So the cold-air supply with return-air intake and hot-air exhaust with ambient-air side must be separated and sealed. Foam tape gasket may be used to seal them. The cooling unit must intake adequate fresh ambient-air to work properly. The ambient-air intake and hot-air exhaust must not be short-circulated.
• • • • • • • • Place the gaskets (1/2” foam tape) on the gasket lips (see Fig. 2.5). If top exhaust, place another gaskets along the top exhaust at the top of the cooling unit (see Fig. 2.6). Move the cooling unit towards the mounting sides and push to press the gaskets. Use 2 mounting brackets and 1/4” screws with 7/16” wrench to secure the cooling unit (see Fig. 2.7). Attach the exhaust wall grille with screws from the rear side of the cabinet (see Fig. 2.8).
Fig. 2.4 MOUNTING SCREW INSERTS Fig. 2.5 REAR EXHAUST GASKETS Fig. 2.
Fig. 2.7 MOUNTING COOLING UNIT Fig. 2.
Temperature and Humidity 1. The controller Fig. 3.1 TEMPERATURE CONTROLLER 1) Keys SET: To display set-point; in programming mode it selects a parameter or confirms an operation. : To start a manual defrost. : To see the maximum stored temperature; in programming mode it browses the parameter codes or increases the displayed value. : To see the minimum stored temperature; in programming mode it browses the parameter codes or decreases the displayed value. : To turn on/off the power to the unit.
4) Alarm Signals The alarm codes are described as follows.
6. Parameter Programming 1) Press and hold the SET + keys until the “°C” or “°F” LED starts flashing, then release the keys. 2) Press and hold again the SET + keys until the Pr2 label is displayed, then release the keys. The first parameter Hy will be displayed. 3) Press up/down keys / to scroll to the required parameter within 10 sec. 4) Press the “SET” key to display its value. 5) Use up/down keys to change its value within 10 sec. 6) Press “SET” to store the new value and the display will flash 3 times.
In case there is excessive frost, the parameters FnC = C-y, idF = 4 and MdF = 20 can be used to avoid frost. 9. How to adjust the humidity The parameter Fon is used to adjust the humidity in the wine cellar. Higher Fon results in higher relative humidity. Use a separate hygrometer to monitor the humidity. 10. How to set alarm call 1) Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the set-point Set.
Care Guide 1. Cleaning Condenser • • • Clean the condenser regularly at least every 6 months. Condenser is located on the ambient air intake side of the cooling unit. Use a condenser brush or a vacuum cleaner with an extended attachment to clean the condenser. 2. Removing Condensate Remove the excessive condensate if it is accumulated on the cooling unit in high humidity conditions. 3. Removing Unit When you remove the cooling unit, beware water may come out of the unit.
Troubleshooting This Troubleshooting Chart is not prepared to replace the training required for a professional refrigeration service person, not is it comprehensive Complaint 1. Unit not running 2. Unit not starting , but temperature rising high 3. Temperature fluctuating 4. Temperature high, unit stopping and starting normally 5. Temperature high, unit stopping and starting with short running time 6. Temperature Possible Causes a. b. c. d. e. f. g. h. i. a.
high or not cooling and running continually b. Cellar too large c. Ambient temperature too high d. Exhaust restricted e. Malfunctioning fans 7. Unit running too long f. Evaporator or condenser airflow g. h. i. j. k. l. Dirty Condenser Iced evaporator Refrigeration system restriction Refrigerant leak Undercharge or overcharge Failed components a. Improper cellar insulation & seal b. Cellar too large c. Ambient temperature higher > 90°F d. Exhaust restricted e. Dirty Condenser f.
low 13.Evaporator freezing up b. c. d. a. b. c. d. e. f. g. h. 14.Water leak a. b. c. d. 15.Excessive condensate in wine cellar 16.Circuit tripping 17.Noisy operation e. a. b. c. a. b. c. a. b.
Wiring Diagram Fig. 6.
Fig. 6.
Customer Support If you need further assistance, please contact us at: Vinotemp International 17631 South Susana Road Rancho Dominguez, CA 90221 Tel: (310) 886-3332 Fax: (310) 886-3310 Email: info@vinotemp.
Warranty Thank you for choosing a Vinotemp cooling unit. Please enter the complete model and serial numbers in the space provided: Model_________________________________________________________ Serial No.______________________________________________________ Attach your purchase receipt to this owner’s manual. 1. Limited Warranty VINOTEMP warrants its products to be free from defects due to workmanship or materials under normal use and service, for twelve months after the initial sale.
is determined to be faulty and is within the twelve month warranty period VINOTEMP will, at its discretion, repair or replace the unit and return it free of charge to the original retail customer. If the unit is found to be in good working order, or beyond the initial twelve month period, it will be returned freight collect. 2. Limitation of Implied Warranty VINOTEMP’S SOLE LIABILITY FOR ANY DEFECTIVE PRODUCT IS LIMITED TO, AT OUR OPTION, REPAIRING OR REPLACING OF UNIT.