Specifications
- 9 - 
4) Alarm Signals 
The alarm codes are described as follows. 
MESSAGE 
CAUSE 
FUNCTION 
P1 
Temperature probe faulty 
Compressor switching to Con and CoF 
HA 
High temperature alarm 
Probe temperature ALU higher than the 
setting temperature; Outputs unchanged 
LA 
Low temperature alarm 
Probe temperature ALL lower than the 
setting temperature; Outputs unchanged 
CA 
External alarm 
All outputs off 
Probe  alarms P1”, start a  few seconds after  the fault in  the  related probe; they 
automatically stop a  few seconds after the probe restarts normal operation. 
Check  connections  before  replacing  the  probe.  Temperature  alarms  “HA”,  “LA” 
automatically stops as soon as the temperature returns to normal value. Alarm 
“CA” (with i1F=PAL) recovers only by switching off and on the instrument.  
2.  Temperature Setting 
  Set the temperature at 55 °F for the optimum aging of wine 
  On  initial  start-up,  the  time  required  to  reach  the  desired  temperature  will 
vary,  depending  on  the  quantity  of  bottles,  temperature  setting  and 
surrounding temperature. 
  Allow 24 hours to stabilize the temperature for each new temperature setting 
operation 
3. How to see temperature set-point 
1) Press and immediately release the SET key, the display will show the set-point 
value. 
2) Press  again and immediately release the  SET  key or wait for 5 seconds to 
display the probe value. 
4. How to change the set-point 
1) Press the SET key for more than 3 seconds until the “°C” or  “°F” LED starts 
blinking and the set-point will be displayed. 
2) To change the set value, press the up/down keys  /  within 10 sec. 
3) To store the new set-point value, press the SET key again or wait 10 sec. 
NOTE: The unit turns on at set-point Set plus regulation differential Hy after anti-
short cycle AC has elapsed; the unit turns off at set-point Set. 