Instructions / Assembly
Installation
10
3.2 Disinfection Procedure
UV disinfection is a physical disinfection process and does not add any potentially harmful chemicals to the water. As UV
does not provide a disinfection residual, it is imperative that the entire distribution system located after the UV be chemically
disinfected to ensure that the plumbing system is free from any bacteriological contaminants. The disinfection process must
be performed immediately after the UV unit is installed and repeated thereafter whenever the UV is shut down for service,
without power, or inoperative for any reason. The procedure for sanitizing the plumbing system is readily accomplished as
follows:
1313
• Connect power.
•
Open all faucet
s and turn
on
water supply
. Inspect
for any
l
eaks.
Note: Outlet must be
protected by a Ground Fault
Circuit Interrupte
r (GFCI).
1
• Ensure only the controller
plug is plu
gged in for entire
disinfection process.
2
2
1
2
2
2
• Shut off the water supply.
• Close each faucet.
3
• Press the pressure button to
release
the pressure from the
cartridges.
4
• Remove sump housing(s)
using sump wren
ch.