Use and Care Manual
General Information
7
2.2 Pipe Lengths
The recommended minimum straight pipe lengths for the various piping configurations are:
Note: Flow Meter Sensor must be mounted in the following orientation with the LED facing up. Ensure all air is purged from
the piping and Flow Meter Sensor. All straight length to the Flow Meter Sensor must be 1.00" in diameter.
6 Solenoid valve
Allows water supply to be shut-off when proper disinfection cannot be assured.
Note: If the ground from your electrical panel is tied to your copper water lines, and you
are using a Plastic Body solenoid valve, installation of an approved ground strap is
required. This ground strap will maintain continuity between the lines that have been cut
to install the solenoid. Check your local electrical code for the correct clamp and cable
size.
7 Sample valve
Allows for sampling of water entering UV chamber; necessary in order to confirm water
being treated is of adequate quality.
8 Plug A stopper provided and installed on Basic models.
9 Sensor Monitors UV output to ensure proper dose (UV exposure) is being provided.
10 UV chamber Provides disinfection of the water. MUST BE INSTALLED VERTICALLY.
11 CoolTouch™ fan Removes excess heat from water in chamber during periods without water flow.
12 Sample valve
Allows for sampling of water immediately following UV treatment; necessary in order to
confirm proper operation of UV system.
13 Shut-off valve Allows maintenance of UV system.
14 Controller
Powers and controls the UV lamp and other devices. Provides human interface,
displaying information and allowing control inputs (such as muting the audible alarm).
15 Power source
Provides power to the controller. For safety reasons the outlet must be protected by a
Ground Fault Circuit Interrupter (GFCI).
Note: To protect the controller, a UL1449 certified (or equivalent) transient voltage surge
suppressor is required.
16 Flow Sensor
Monitors flow to provide real time dose (UV exposure) Flow Meter Sensor must be
installed in this orientation with the LED facing up. (PRO10, PRO20, PRO30 only)
Item L S (minimum) O A (maximum) B C D
PRO10 21.4” (55 cm) 12” (30 cm) 4” (10 cm) 72” (182 cm) 6.5” (16.5 cm) 13” (33 cm) 48” (122 cm)
PRO20, H+, H 31" (78 cm) 12” (30 cm) 4” (10 cm) 72” (182 cm) 6.5” (16.5 cm) 13” (33 cm) 48” (122 cm)
PRO30 41" (103 cm) 12” (30 cm) 4” (10 cm) 72” (182 cm) 6.5” (16.5 cm) 13” (33 cm) 48” (122 cm)
PRO50, K+, K 41" (103 cm) 12” (30 cm) 4” (10 cm) 72” (182 cm) 6.5” (16.5 cm) 13” (33 cm) 48” (122 cm)
Straight Flange 10" straight pipe
Reducing Flange 15" straight pipe 2 x 90 degree Elbows 25" straight pipe
2 x 90 degree Elbows 3 dimensions 40" straight pipe Pump 50" straight pipe