9,67$ 6( 6HFXULW\ 6\VWHP ,QVWDOODWLRQ DQG 6HWXS *XLGH * ALARM CHECK FIRE AWAY STAY INSTANT BYPASS NO AC CHIME BAT ARMED READY NOT READY OFF 1 MAX AWAY STAY 2 3 TEST BYPASS 4 5 6 INSTANT CODE CHIME 7 8 9 0 # READY * PANIC •• • •• •• •• • • •• •••• •• ® N7227V5 10/00
RECOMMENDATIONS FOR PROPER PROTECTION The following recommendations for the location of fire and burglary detection devices help provide proper coverage for the protected premises. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Table of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • SECTION 1. Introduction............................................................................................................................ 1–1 Description ........................................................................................................................................................1-1 Features.................................................................
SECTION 11. Final Power-Up .................................................................................................................... 11–1 Earth Ground Connections ............................................................................................................................11-1 Wiring the AC Transformer ...........................................................................................................................11-1 AC Power-Up ...........................................
S E C T I O N 1 Introduction • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Description ♦ Features • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Description The VISTA–10SE is a control that supports up to 22 hardwired and wireless zones, plus remote keypads.
VISTA-10SE Installation and Setup Guide Security Codes • One Master code for entire system (User 2). Installer code is User 1. • 4 secondary user codes (Users 3–6). • One duress code (User 8). Duress Code: An emergency code that, when used to disarm or arm the system, will send a silent duress message to the central station. Keypad Panic Keys • Up to 3 programmable panic key functions are provided. • Designated as Zones 7, 95, 96. • Activated by wired and wireless keypads. • Reported separately.
Section 1 - Introduction Alarm Output • Provides a 12VDC, 2 AMP output that can drive the compatible sounders listed in the EXTERNAL SOUNDERS section (assumes a fully charged battery is connected). • Steady output for burglary/panic, or temporal pulse sounding output for fire notification, as required by UL. • Uses current-limiting circuitry for protection. Auxiliary Power Output • Provides 12VDC, 500mA maximum. Uses current limiting circuitry for protection.
VISTA-10SE Installation and Setup Guide 1-4
S E C T I O N 2 Installing the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Mounting the Cabinet ♦ Installing the Lock ♦ Mounting the Control and RF Receiver Circuit Board in the Cabinet ♦ Standard Phone Line Connections ♦ Mounting the Control's Circuit Board Alone in the Cabinet • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Mounting the Cabinet Mount the control cabi
VISTA-10SE Installation and Setup Guide Mounting the Control's Circuit Board Alone in the Cabinet To mount the circuit board alone in the cabinet, follow these steps: 1. Hang two mounting clips* (provided) on the raised cabinet tabs (see Detail B in Figure 2 below). 2. Insert the top of the circuit board between the rows of slots at the top of the cabinet as shown in Detail A. 3. Position the base of the board onto the mounting clips and secure both to the cabinet with the supplied screws (see Detail B).
Section 2 - Installing the Control HOLES FOR ANTENNAS AND GROUNDING LUGS CABINET CIRCUIT BOARD BOARD SUPPORTING SLOTS RECEIVER CIRCUIT BOARD (See Detail D) + DETAIL A SIDE VIEW OF BOARD SUPPORTING SLOTS + MOUNTING CLIP CONTROL CIRCUIT BOARD MOUNTING CLIP SCREW (2) GROUNDING LUG (2) ANTENNA (2) DETAIL B SIDE VIEW OF MOUNTING CLIP CABINET DETAIL C SIDE VIEW OF MOUNTING CLIP RCVR BRD + + ANTENNA MOUNT (2 PLACES) DETAIL D ANTENNA AND GROUNDING LUG INSTALLATION V10SE-004-V0 Figure 3.
INCOMING TELECOM LINE HANDSET 17 18 19 20 GROUND VISTA-10SE Installation and Setup Guide 21 RING PLUG INCOMING TELECOM LINE TIP RED (RING) GREEN (TIP) EARTH GROUND GREY (RING) BROWN (TIP) TERMINALS ON CONTROL TIP RJ31X JACK RING DIRECT CONNECT CORD PREMISES PHONES V10SE-024-V0 Figure 4.
S E C T I O N 3 Remote Keypads • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Keypads That May Be Used ♦ Supplementary Power for Additional Keypads ♦ Wiring to the Keypads ♦ Preliminary Checkout Procedure ♦ Mounting the Keypads • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section lists the wired keypads that may be used and provides instructions for wiring and mounting t
VISTA-10SE Installation and Setup Guide Wiring Run Chart for Devices* Drawing Aux Power From the Control (12V+ & 12V–) TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN Wire Size #22 #20 #18 #16 50mA or less 500 ft (152m) 750 ft (228.6m) 1300 ft (396m) 1500 ft (457m) 100mA 250 ft (76m) 380 ft (116m) 650 ft (198m) 1000 ft (305m) 300mA 80 ft (24m) 130 ft (39.6m) 220 ft (67m) 330 ft (100.5m) 500mA 50 ft (15m) 80 ft (24m) 130 ft (39.
Section 3 - Installing Remote Keypads Keypads powered from supplies that do not have a backup battery will not function when AC power is lost. Therefore, be sure to power at least one keypad from the Control's auxiliary power output. Connect the additional keypads as shown in Figure 6, using the keypad wire colors shown. Be sure to observe the current ratings for the power supply used. Make connections directly to the screw terminals as shown in Figure 6.
VISTA-10SE Installation and Setup Guide If the “Ready” message is not displayed on any of the keypads in the system, or a “Not Ready” message is displayed, check the keypad wiring connections, and make sure each of the 6 basic hardwired zones has a 1000 ohm resistor connected across its terminals. Do not remove the EOL resistors until you are ready to make connections to the hardwired zones, to allow for testing later in the manual.
S E C T I O N 4 Basic Hardwired Zones 1–6 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Installing the Hardwired Zones ♦ Programming Hardwired Zones • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Installing the Hardwired Zones Common Characteristics for Zones 1–6 UL • Response time from 300 - 500 milliseconds (400 milliseconds nominal).
VISTA-10SE Installation and Setup Guide 3. To meet NFPA 72 requirements, you must use a supervisory module to supervise power (e.g., System Sensor No. A77-716B Relay module). AUX PWR OUTPUT TERMINALS + 5 _ 4 BLK + _ + 4-WIRE SMOKE OR COMBUSTION DETECTORS + _ _ VIOLET TO HI SIDE OF TO LO SIDE _ EOL POWER SUPERVISION RELAY MODULE A77-716B 1000 OHMS EOLR + ZONE 5 RED HEAT DETECTOR HEAT DETECTOR V10SE-010-V0 Figure 7.
S E C T I O N 5 Wireless Expansion (5800 System) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Wireless Expansion ♦ About Jam Detection and Reporting ♦ Installing the 5881/5882 Receiver ♦ 5800 Series Transmitters ♦ Installing the 5800TM Module ♦ Installing 5800 Series Transmitters • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Wireless Expansion The VISTA-10SE su
VISTA-10SE Installation and Setup Guide Installing the 5881/5882 Receiver RF System Installation Advisories Follow the guidelines below when installing the RF receiver. (Disregard if the receiver is mounted in the control cabinet.) • Place the RF receiver in a high, centrally located area for best reception. • Do not locate the receiver or transmitters on or near metal objects. This decreases range and/or block transmissions.
Section 5 - Wireless Expansion Installing the 5800TM Module Installation of this module is necessary only if you are using one or more 5827BD Wireless Bi-directional keypads, 5804 or 5804BD Transmitters (wireless keys). Mounting the 5800TM Module The 5800TM must be located next to the RF receiver (between one and two feet from the receiver’s antennas). The 5800TM must not be installed within the control cabinet. Mount the unit using its accompanying mounting bracket.
VISTA-10SE Installation and Setup Guide For button transmitters (RF keys), such as the 5801, 5804, and 5804BD, you must assign a unique zone number to each individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop or input number, which is automatically displayed on the keypad. Programming an RF House ID Programming an RF House ID (01–31) in field ✱24 is necessary only if you are using 5827 or 5827BD Wireless Keypads or 5804BD Transmitters.
Section 5 - Wireless Expansion The wireless system can identify a true low-battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system. Some transmitters (e.g., 5802, 5802CP, and 5804) contain long-life but nonreplaceable batteries, and no battery installation is required. At the end of their life, the complete unit must be replaced (and a new serial number enrolled by the control).
VISTA-10SE Installation and Setup Guide 5800 Series Transmitters Table (continued) Model Description Input Type and Special Notes 5817 (cont'd.) Multi-Point Universal Transmitter (cont'd.) DIP Switches: 5818 Recessed Magnetic Contact Transmitter Shock Processor Transmitter 5819 5819BRS 5819WHS 5849 5850 5852 5890 5890P1 Set all DIP switches to the OFF position when enrolling the serial number. NOTE: All loops must be assigned the same input type. Enroll as “3” for RF (supervised).
S E C T I O N 6 Relay Output Devices • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Relay Device Basics ♦ Programming Options ♦ 4204 Relay Modules • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Relay Device Basics Relays are programmable switches that can be used to perform many different functions.
VISTA-10SE Installation and Setup Guide 4204 Setup The 4204 unit can be mounted either remotely or in the control panel. The following steps should be taken to properly set up the 4204: OFF ON ON 1 2 3 4 5 1. Connect the 4204 to the control's remote keypad terminals (4–7), using the connector supplied with the 4204. Use standard 4-conductor twisted cable for long wiring runs.
S E C T I O N 7 4285 and 4286 VIP Module • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Installing the VIP Module ♦ Checking 4285/4286 VIP Module Operation ♦ Programming the 4285/4286 VIP Module • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Installing the (Voice Interactive Phone) Module General Information The 4285/4286 VIP Module is an add-on accessory for the VISTA–10SE that
VISTA-10SE Installation and Setup Guide VIP Module Wiring The VIP Module is wired between the control panel and the premises handset(s). It listens for touch-tones on the phone line and reports them to the control panel. During on-premises phone access, it powers the premises phones; during off-premises phone access, it seizes the line from the premises phones and any answering machines.
Section 7 - 4285/4286 VIP Module 4285/4286 VIP Module WIRING NOTES: 1. Wire the VIP Module exactly as shown, using a direct-connect cord and RJ31X jack. 2. If you do no hear tones when pressing keys after accessing the security system via an on-premises phone, try reversing the pair of wires connected to terminals 3 and 4 on the VIP Module and the pair of wires connected to terminals 17 and 18 on the control. 3.
VISTA-10SE Installation and Setup Guide Programming the Control for Phone Access To program the control for phone access using the 4285/4286 VIP Module, you must assign a VIP Module access code (✱26) and ring detection count (✱95). Also, you may optionally select words and/or form custom words that would be displayed on the keypad. Refer to THE DATA FIELD DESCRIPTION and ALPHA DESCRIPTOR PROGRAMMING sections for specific programming details. Perform a preliminary check of the VIP Module, as indicated next.
S E C T I O N 8 External Sounders • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Compatible Sounders ♦ Sounder Supervision ♦ NFPA Requirements ♦ Testing the Sounder ♦ Sounder Connections and Power • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Compatible Sounders ADEMCO AB-12M 10” Motorized Bell & Box Motor bell & box. UL Grade A. 100mA current draw.
VISTA-10SE Installation and Setup Guide Sounder Connections and Power The VISTA-10SE provides a 12VDC output, which can power external alarm sounders, bells, or sirens (see table of compatible sounders on a previous page). This output activates a sounder when an alarm occurs. Make connections to alarm output terminals 3 (+) and 4 (–). See Figure 12 below. UL The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600mA.
S E C T I O N 9 Long-Range Radio • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Long-Range Radio ♦ Programming for Long-Range Radio ♦ Wiring Connections ♦ Dynamic Signaling Feature • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Long-Range Radio If output to Long-Range Radio (LRR) is selected, all messages that are programmed to go to the primary telephone line recei
VISTA-10SE Installation and Setup Guide Dynamic Signaling Feature This VISTA-10SE control panel features Dynamic Signaling Delay (DSD) and Dynamic Signaling Priority (DSP) message reporting when Long-Range Radio is used. These message outputs are accessed through data field ✱93. The Dynamic Signaling feature is designed to reduce the number of redundant reports sent to the central station.
S E C T I O N 1 0 Audio Alarm Verification (AAV) Unit • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Audio Alarm Verification ♦ Wiring Connections • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Audio Alarm Verification An Audio Alarm Verification (AAV) module, such as the Eagle 1250, is an add-on accessory that permits voice dialog between an operator at a central sta
VISTA-10SE Installation and Setup Guide EARTH GROUND CONTROL EAGLE SUPPLIED CABLE 4 17 18 19 20 21 5 RED (R) GREEN (T) GREY (R) BROWN (T) ➤ ➤ RJ31X CONTROL/ DIALER HEADER RED ON 123456 13 V+ 14 15 GND 16 BROWN 4204 RELAY 1 SHOWN OFF TO PREMISES HANDSET YELLOW DIP Switch INCOMING PHONE LINE NO NC C • •• • • NOTE: REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE. EAGLE 1250 TIP RING V10SE-027-V0 Figure 15.
S E C T I O N 1 1 Final Power-Up • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Earth Ground Connections ♦ Calculating the Battery Size Needed ♦ Wiring the AC Transformer ♦ Connecting the Backup Battery ♦ AC Power-Up ♦ Battery Tests • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Earth Ground Connections The designated earth ground terminal (21) must be terminated in a good ea
VISTA-10SE Installation and Setup Guide AC Power-Up To turn on AC power, perform the following steps: 1. Plug the 1321/1321CN into a 24-hour, unswitched 120VAC outlet. Following power-up, one of the following is displayed on the keypad: AC, dI (disabled); BUSY STANDBY (on alpha keypads); or NOT READY (on fixed-word keypads). The green POWER LED (or READY LED on some keypads) should light. 2. After approximately 1 minute, the initial displays revert to DISARMED...
Section 11 – Final Power-Up Connecting the Backup Battery In the event of an AC power loss, the control panel is supported by a backup, rechargeable Sealed Lead Acid battery. The range of battery sizes recommended are: 12VDC; 4AH17.2AH. See "Calculating the Battery Size Needed" earlier in this section. The battery is installed in the control cabinet. Making the Battery Connections 1. Use the battery standby formula (above) to select the appropriate battery for the installation.
VISTA-10SE Installation and Setup Guide 11-4
S E C T I O N 1 2 Mechanics of Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Programming ♦ Interactive Menu Mode Programming ♦ Entering Program Mode ♦ Loading Factory Defaults ♦ Programming a Data Field ♦ Programming System Setup Fields ♦ Reviewing a Data Field/Erasing an Entry ♦ Exiting the Programming Mode • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
VISTA-10SE Installation and Setup Guide If a different Installer code is subsequently programmed, use it instead of 4111 to gain access to the Programming mode. When you enter the Program mode, data field ✱20 is displayed (this is the first data field in the system). The system now accepts entries for field ✱20. Programming a Data Field 1. Press [✱]+ Field No. (for example, ✱21), then make the desired entry. 2.
S E C T I O N 1 3 Zone Response Type Definitions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Zone Type Definitions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Zone Type Definitions You must assign to each zone a zone type that defines the way in which the system responds to faults in that zone. Zone types are defined below.
VISTA-10SE Installation and Setup Guide Type 05 Trouble by Day/ Alarm by Night Zone type 05 is usually assigned to a zone that contains foil-protected doors or windows; or covers a sensitive area (e.g., stock room, drug supply room, etc.) It can also be used on a sensor or contact in an area where immediate notification of an entry is desired. Zone Characteristics: • Provides an instant alarm when armed in AWAY, STAY, INSTANT, or MAXIMUM (night) mode.
Section 13 – Zone Response Type Definitions Type 20 Arm–STAY Zone type 20 is a special-purpose zone type used with 5800 Series wireless pushbutton transmitters. Zone Characteristics: Type 21 Arm–AWAY • Exit delay regardless of the arming mode selected. • System is armed in the STAY mode when the zone is activated. • Zone number is sent to the central station as a user number when arming or disarming. Zone type 21 is a special-purpose zone type used with 5800 Series wireless pushbutton units.
VISTA-10SE Installation and Setup Guide 13-4
S E C T I O N 1 4 Data Field Descriptions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Descriptions of System Data Fields • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • NOTE: The following program field must be programmed before doing any zone programming: ✱22 RF SYSTEM Descriptions of System Data Fields The blank programming form (separate insert) should be used to record the
VISTA-10SE Installation and Setup Guide ✱26 VOICE (PHONE) MODULE ACCESS CODE (2-Digit Entry) The use of a 4285 or 4286 VIP (Phone) Module requires a 2-digit code. Enter a 2-digit phone access code as follows: For first digit, enter any digit from 1 to 9; for second digit, enter # +11 for ✱, or # +12 for #. Example: If the desired access code is 7✱, 7 is the first entry, and # + 11 (for ✱) is the second entry. 00 = VIP Module disabled. 4285/4286 VIP Module.
Section 14 – Data Field Descriptions ✱39 AUDIBLE EXIT WARNING (1-Digit Entry) If enabled, this field provides exit warning sound when armed AWAY or MAXIMUM. Warning sound consists of slow continuous beeps until last 5 seconds, when it changes to fast beeps. The warning sound will end at the termination of Exit time. 0 = no; 1 = yes. DIALER PROGRAMMING (✱40–✱50) Fields ✱40, ✱41, ✱42: ✱40 PABX ACCESS CODE (See box at left.) Enter up to 4 digits if PABX is needed to access an outside line.
VISTA-10SE Installation and Setup Guide ✱46 REPORT FORMAT (1-Digit Entry) Determine which format is to be used to report to the central station. Enter 1 digit (0–9). 0 = 3+1; 4+1 ADEMCO Lo Speed Standard (this is the default) For an explanation of these formats, see the SYSTEM COMMUNICATION section.
Section 14 – Data Field Descriptions A 10-digit code is sent to the pager that is coded in the following format: 4-digit Subscriber No. SSSS–EEE–NNN 3-digit User or Zone No. (as entered in field ✱43) 3-Digit Event Code (EEE), as follows: 911 = Alarm (NNN = Zone No.) 001 = Open, System disarmed (NNN = User No.) 002 = Close, System armed ( NNN = User No.) 811 = Trouble ( NNN = Zone No.) NOTE: The first digit of the Subscriber No. entered in field ✱43 must be 1–9 (do not use 0); the last 3 digits can be 0–9.
VISTA-10SE Installation and Setup Guide ✱52 ZONE 3 RESPONSE TIME TO OPEN (1-Digit Entry) 0 = 400mS nominal; 1 = 10mS nominal. ✱56 ZONE ASSIGNMENT/ALARM REPORT CODES This is an Interactive Menu mode that is used to program zone numbers, zone types, and alarm and report codes, and to identify the type of loop input device. This mode can also be used for entering 5800 Series transmitter serial numbers (serial numbers can also be entered using the Expert Programming Mode in ✱58).
Section 14 – Data Field Descriptions SYSTEM STATUS ✱60 REPORT CODES (✱60 –✱68) ✱61 ✱62 TROUBLE REPORT CODE (See box above.) (2-Digit Entry) BYPASS REPORT CODE (See box above.) (2-Digit Entry) AC LOSS REPORT CODE (See box above.) (2-Digit Entry) Reports with Subscriber No. Timing of this report is random with up to a 48-minute delay. The Restore Report has a random delay of up to about 12 minutes. If AC restores before the report goes out, there is no AC Restore Report.
VISTA-10SE Installation and Setup Guide RESTORE REPORT CODES (✱70 – ✱75) ✱70 ALARM RESTORE REPORT CODE (See box on previous page). For expanded or 4+2 reporting, a 2nd digit is automatically sent, and is the same as the 2nd digit of the zone Alarm Report code programmed in field ✱56. ✱71 TROUBLE RESTORE REPORT CODE (2-Digit Entry) (See box on previous page.) This is sent when a trouble in a zone is restored. ✱72 BYPASS RESTORE REPORT CODE (2-Digit Entry) (See box on previous page.
Section 14 – Data Field Descriptions ✱93 DYNAMIC SIGNALING DELAY (DSD) (1st entry) This field enables you to select the time the panel should wait for acknowledgment from the first reporting destination before it attempts to send a message to the second destination. Delays can be selected from 0 to 225 seconds, in 15-second increments. This delay is per message. 0–15 times a 15-second delay. e.g., 1 = 15 seconds, 2 = 30 seconds, etc. Default is “0” (no delay). You must enter “0” for UL installations.
VISTA-10SE Installation and Setup Guide Important Note: If “15” is entered in field ✱95 to bypass an answering machine, and a 4285/4286 VIP Module is included in the installation, you should note the following: When calling in from an off-premises phone (to receive a status report or execute a command), the user should make the initial call, allow 1 to 3 rings only, and hang up. Then call in again.
S E C T I O N 1 5 Zone Programming (✱56/✱58 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Zone Programming ♦ To Remove a Zone ♦ ✱56 Zone Programming Mode Procedures ♦ To Delete a Transmitter Serial Number ♦ ✱58 Expert Programming Mode Procedures ♦ To Enter and Duplicate Wireless Keys • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming ✱56
VISTA-10SE Installation and Setup Guide È Zone Number 10 Zone Type Perimeter 03 Zone Type Ç Zone Type (ZT): Enter the Zone Type response (or change it, if necessary). Each zone must be assigned to a zone type, which defines the way in which the system responds to faults in that zone. Enter the Zone Type code (or change it, if necessary). Zone types are listed below. NOTE: If you enter 00, Delete Zone ? is displayed.
Section 15 - Zone Programming 10 INPUT S/N: A022-4064 L Serial number Entry and Loop Number Entry. 1 Used only when enrolling wireless transmitters. Note: The [A] and [B] keys may be used to move the cursor to the right (A) or left (B) within the serial number field, thus allowing you to correct any entry errors that may have been made. a. Transmit an open and close sequence. If using a button-type transmitter, press and release the button; OR b.
VISTA-10SE Installation and Setup Guide 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated on this page have one or more unique factory-assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four input loops require four programming zones). LOOP 3 LOOP 2 LOOP 1 (REED) (PRIMARY) LOOP 2 LOOP 1 (TERMINALS) LOOP 1 LOOP 4 YOU MUST ENROLL THIS BUTTON 2 (AUX. CENTER) 3 LOOP 1 5802MN ENROLL AS "UR" OR "RF" (AUX.
Section 15 - Zone Programming Confirmation Option: This prompt appears only if you answered Yes to the first prompt in this section. The system enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate the loop input or button that corresponds to this zone. XMIT TO CONFIRM PRESS ✱ TO SKIP We recommend that you confirm the programming of every transmitter before proceeding to the next zone.
VISTA-10SE Installation and Setup Guide ✱58 Expert Programming Mode Procedures Enter the Program mode and follow the step-by-step instructions below. NOTE: Before proceeding, you must program field ✱22 (RF System) as required. SET TO CONFIRM? Press ✱58. This display appears upon entry into this mode. 0 = NO The default is 0 (No). 1 = YES 0 If you enter 1 (Yes), you are prompted to confirm each transmitter after entering the serial and loop numbers (see “XMIT TO CONFIRM” prompt on a following page).
Section 15 - Zone Programming 10 INPUT S/N: A022-4064 L Serial Number entry and Loop Number entry. 1 Used only when enrolling wireless transmitters. Note: The [A] and [B] keys may be used to move the cursor to the right (A) or left (B) within the serial number field, thus allowing you to correct any entry errors that may have been made. a. Transmit an open and close sequence. If you are using a buttontype transmitter, press and release the button; OR b.
VISTA-10SE Installation and Setup Guide To Remove a Zone To either temporarily or permanently remove a zone from the 5800 system: 1. Enter the programming mode: Key Installer Code + 8 + 0 and press ✱56. SET TO CONFIRM? 0 = NO 1 = YES 0 Enter Zn Num. (00 = Quit) 10 2. The display at left appears. Enter 0 for No; 1 for Yes. 3. The display at left appears. Enter zone number to be removed. Example: 10. Press [✱] to continue. Zn ZT RC In: 10 03 This summary display at left appears. Press [✱] to continue.
Section 15 - Zone Programming If you want to replace the serial number continue to step 4; otherwise, skip to step 7. A display for the new transmitter number appears. 10 INPUT S/N: L AXXX-XXXX 1 4. Key the transmitter. The new transmitter serial number replaces the X’s in the display. 5. The new summary display appears with a small “s” next to the loop number to indicate that the new transmitter serial number has been learned.
VISTA-10SE Installation and Setup Guide 10. If necessary, press the [#] key to back up without saving, and reenter the serial number. If you are manually entering the serial number, use the [A] key to move forward within the screen, and the [B] key to move backward. 11. If you entered “Yes” at the SET TO CONFIRM? prompt previously (see first prompt following entry into the ✱56 or ✱58 Programming Mode), the display on the left appears. Confirm serial and loop numbers by activating the wireless key.
Section 15 - Zone Programming Wireless Key Predefined Default Templates LOOP 3 YOU MUST PROGRAM THIS BUTTON LOOP 4 ON OFF GREEN/YELLOW LED LOOP 2 LOOP 2 RED/YELLOW LED LOOP 1 LOOP 4 (YOU MUST PROGRAM THIS BUTTON) LOOP 3 LOOP 1 •• • •• •• • • •• • •• • •• •• ENROLL AS "BR" ENROLL AS "BR" 5804 Wireless Key Transmitter 5804BD 2-Way Wireless Key Transmitter For 5804 TEMPLATE 1 TEMPLATE 2 TEMPLATE 3 UL Loop Function For 5804BD Zone Type TEMPLATE 4 Loop Function Zone Type No Response
VISTA-10SE Installation and Setup Guide 15–12
S E C T I O N 1 6 Output Device Programming (✱80 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Programming Options Defined ♦ Programming Output Devices • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Programming Options Defined The following definitions will help you understand the programming of output devices when using ✱80 (this section) and ✱81 (the Zone List secti
VISTA-10SE Installation and Setup Guide • TROUBLE Relay action begins upon any trouble condition in an assigned zone in the zone list. • NOT USED Relay action is not dependent upon one of the above events. 2. ZONE LIST (ZL) is a group of zones to which the “EVENT” applies in order to activate a particular relay.
Section 16 - Output Device Programming If a relay is energized before a 4-wire smoke detector is reset, the relay will be stopped by the interruption of Aux. Power that resets the smoke detector. If this is not desired, the power to the relay unit should be supplied from another 12V power source (e.g., the same source that is powering external equipment through the relay contacts). Programming Output Devices 1.
VISTA-10SE Installation and Setup Guide 02 Start: No List 02 Start: Not Used Zn List 0 Zn Typ 00 If a zone list will be used to START the relay action, enter the zone list number (to be programmed in field ✱81): 1, 2, or 3. If not used, enter 0. Press the [✱] key to continue. If a zone type or system operation will be used to START the relay action, enter the appropriate two-digit code (see table that follows). If not, enter 00. Press the [✱] key to continue.
S E C T I O N 1 7 Zone Lists (✱81 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Zone List Menu Mode ♦ Zone List Displays • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone List Menu Mode Zone List Menu mode is used to program zone lists for output devices (programmed in ✱80 Menu mode).
VISTA-10SE Installation and Setup Guide Notes: • Any list may include any or all of the system's zone numbers. • A zone list can be assigned to more than one output relay. • If you only want to review what has been programmed previously, press #81. The review can be advanced by using the ✱ key. When finished, press 00✱ to quit. No programmed values can be changed in this mode. When programming in ✱80 and ✱81 Interactive modes is completed, exit the programming mode by keying ✱99.
S E C T I O N 1 8 Alpha Descriptor Programming (✱82 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Alpha Descriptor Programming ♦ Programming Zone Descriptors ♦ Zone Descriptors ♦ Adding Custom Words • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Alpha Descriptor Programming This Interactive mode section provides instructions for programming alpha descrip
VISTA-10SE Installation and Setup Guide 2. Enter ✱82. The “Program Alpha ?” prompt appears. Program Alpha ? 0 = No, 1 = Yes 0 3. By pressing 1 (Yes) in step 2 above: Custom Words ? 0 = No, 1 = Yes If you press 0 (No), proceed to step 4. 0 The “Custom Words ?” prompt appears. Proceed to the six steps for Adding Custom Words later in this section. 4. By pressing 0 (No) in step 2: The system then automatically displays the default descriptor for zone 01.
Section 18 – Alpha Descriptor Programming ✱ ZN 01 9. Press [6] to accept the selected word. BACK NOTE: If these are the only words you are using for the descriptor, press [8] instead of [6] to save them in memory. DOOR A ↑ Flashing Cursor if “6” is pressed (system is ready for next word). 10. The two words in our example have now been entered. Note, however, that up to three words may be entered (provided the number of characters will fit on the screen). Press [8] to save all words in memory.
VISTA-10SE Installation and Setup Guide 5. Repeat steps 3 and 4 to create the desired word(s). Note that the [4] key can be used to move the cursor to the left. Use the [6] key to make a space between characters. Remember, no word or wordstring can exceed 10 characters including spaces. 6. Press the [8] key to save the custom word(s) and return to the "CUSTOM WORD ?" display. The custom word(s) you entered will automatically be added to the built-in vocabulary.
Section 18 – Alpha Descriptor Programming ALPHA VOCABULARY LIST (For Entering Zone Descriptors) NOTE: Some rarely used words appearing in previously published lists have been deleted from the list below. Use only this list for 000 • 001 • 002 004 005 • 006 • 007 • 009 010 • • • • • • • 012 013 014 016 017 018 019 020 • 021 • 022 023 025 • 026 028 • 029 030 031 033 034 035 036 • 037 038 • 040 • 046 047 • 048 049 • 050 051 • 052 • 053 054 selecting zone descriptors.
VISTA-10SE Installation and Setup Guide 18-6
S E C T I O N 1 9 Remote Programming and Control (Downloading) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Remote Programming ♦ Equipment Required • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Remote Programming The VISTA–10SE can be remotely programmed from an IBM compatible Personal Computer (PC) a modem, and ADEMCO’s Compass Windows downloading software.
VISTA-10SE Installation and Setup Guide Equipment Required At the premises: VISTA–10SE and keypad. At the installer's office/home: An IBM PC-compatible computer. Either a SMARTMODEM 1200 (Level 1.2 or higher external or Level 1.1 or higher [with 4 position DIP switch] internal style), or an Optima 24 Plus FAX96 Modem. ADEMCO’s Compass Windows downloading software. Appropriate interconnecting cables.
S E C T I O N 2 0 System Communication • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Panel Communication with Central Station ♦ System Communication Programming ♦ Report Code Formats • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Panel Communication with Central Station This section provides an explanation of formats this system accommodates for reporting alarms and other system con
VISTA-10SE Installation and Setup Guide The following describes each format in greater detail. 3+1 and 4+1 Standard Formats Comprise a 3- (or 4-) digit subscriber number and a single-digit report code (e.g., Alarm, Trouble, Restore, Open, Close, etc.). 3+1 and 4+1 Expanded Formats Comprise a 3- (or 4-) digit subscriber number, and a two-digit report code. The first digit is displayed on the first line. On the second line, the first digit is repeated 3 (or 4) times and is followed by the second digit.
S E C T I O N 2 1 System Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Security Codes ♦ Exit Error Alarm Displays ♦ Keypad Functions ♦ Trouble Conditions ♦ 4285/4286 VIP Module • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Security Codes Installer Code The installer programs the 4-digit Installer Code initially as part of the programming procedure.
VISTA-10SE Installation and Setup Guide Duress Code This feature is intended for use when you are forced to disarm or arm the system under threat. When used, the system will act normally, but can silently notify the central station of your situation, if that service has been provided. Important: This code is useful only when the system is connected to a central station. The Duress code may be any 4-digit code assigned to User Number 8. To program a Duress code 1. Enter Master Code. 2.
Section 21 – System Operation Arming INSTANT .............. Enter code + INSTANT [7]. Arming MAXIMUM............ Enter code + MAXIMUM [4]. Quick Arming ..................... Simply press [#] key in place of code, then press AWAY, STAY, INSTANT, or MAXIMUM to arm system as (if enabled) desired. Note that the [#] key cannot be used in place of code when disarming the system. Disarming............................ Enter code + OFF [1]. Bypassing Zones ................ Enter code + BYPASS [6] + zone number(s).
VISTA-10SE Installation and Setup Guide 4285/4286 VIP Module (if used) Refer to the separate instructions supplied with the VIP Module for information concerning its operating procedures. Relay Outputs (if used) If relay outputs are used, two keypad entries available to the user are included among the system operation choices (34 and 35) that may be programmed (see the OUTPUT DEVICE PROGRAMMING section).
Section 21 – System Operation • A display of BAT (on fixed-word keypads) or SYSTEM LO BAT (on alpha keypads) with no zone number indicates that the system's main standby battery is weak. • A display of "BAT" (on fixed-word keypads) or “LO BAT” (on alpha keypads) with a zone number and a once per minute "beeping" at the keypad indicates that a lowbattery condition exists in the wireless sensor displayed (zone "00" indicates a wireless keypad).
VISTA-10SE Installation and Setup Guide 21-6
S E C T I O N 2 2 Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Test Procedures ♦ Go/No Go Test ♦ Transmitter Sniffer Mode • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Test Procedures After installation is completed, the system should be carefully tested, as follows: 1. With the system in the disarmed state, check that all zones are intact.
VISTA-10SE Installation and Setup Guide If a key (or key pair) has been programmed for fire, the keypad and external sounder will emit an interrupted alarm sound, and ALARM, FIRE and zone number will be displayed. Silence alarms by entering the security code and pressing [OFF] key. 9. If Output Relay Units have been installed, test their programmed action. 10. Notify the central station when all tests are finished, and verify results with them.
S E C T I O N 2 3 Specifications & Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Specifications ♦ Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Specifications VISTA 10SE Security Control 1. Physical: 12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, ADEMCO No.
VISTA-10SE Installation and Setup Guide Accessories (Compatible Devices) No. 1321 16.5VAC, 25VA Plug-In Transformer (in USA) No. 1321CN 16.5VAC, 25VA Plug-In Transformer (in Canada) Sounders ADEMCO AB-12M 10” Motorized Bell & Box Motor bell & box. UL Grade A. 100mA current draw. ADEMCO 1011BE12M 10” Motorized Bell & Box Motor bell & box. UL Listed. 100mA current draw. ADEMCO 702 Outdoor Siren Self-contained 6–12 volt siren (driver built-in) and weatherproof for outdoor use.
A P P E N D I X A Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use.
VISTA-10SE Installation and Setup Guide UL NOTICES 1. This is a "Grade A" residential system. 2. The 4285/4286 VIP Module and 7720PLUS or 7820 Long-Range Radios have not been UL tested and cannot, therefore, be used in a UL installation. 3. The Entry Delay (field ✱38) cannot be greater than 45 seconds for UL installations. 4. The maximum number of reports per armed period (field ✱92) must be unlimited (set to 1) for UL installations. 5.
A P P E N D I X B Limitations and Warranties • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: • Intrusion detectors (e.g.
VISTA-10SE Installation and Setup Guide ADEMCO LIMITED WARRANTY Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates (“Seller”), 165 Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product or, for products not having an ADEMCO date stamp, for
+ – ALARM OUTPUT 10.5-13.8VDC, 2A MAX. (600mA MAX. FOR UL USAGE, INCLUDING AUX. POWER) STEADY FOR BURGLARY/PANIC, TEMPORAL SOUNDING FOR FIRE (e.g. USE ADEMCO 740 SOUNDER, 702 OR 719 SIREN, OR 12V BELL) CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE EMERGENCY NUMBER.
165 Eileen Way, Syosset, New York 11791 Copyright © 2000 PITTWAY CORPORATION ¬1 9 Wl N7227V5 10/00