Electric Point Machine Westinghouse Style M70 MKIII  TMG E1583 
4.1  Motor 
4.1.1  Description 
The point machine is fitted with a plug-connected series-wound motor, as shown in 
Figure 4.1.1. The split field enables a regenerative braking circuit to provide snubbing 
at the end of the stroke. The plug connector is indexed to prevent use of a wrong type 
motor. If required, the machine can also be fitted with a 110V DC, AC immune 
permanent magnet motor. 
4.1.2  Removal and Replacement 
1.  Unplug the lead from the terminal board. 
2.  Remove the two bolts from the baseplate. 
3.  Slide the motor towards the end of the machine until the spur gear disengages 
from the gear cluster and then remove the motor. 
4.  Replacement involves the above procedures in reverse order. Care should be 
taken to ensure that the spur gear meshes properly and that the location spigot 
seats properly before bolting down. 
4.1.3  Overhaul 
The operation of the motor should be observed during normal monthly maintenance 
visits. If it shows signs of abnormal noise, slackness in the bearings or heavy burning 
of the commutator, the motor should be exchanged. 