Owner`s manual
15
VITA SPA
ENGLISHFRANÇAIS
240 Volt Installation
Permanently Connected:
The Models Amour, Intrigue, & Image
(Blower or Circ Pump Option) come factory
set for 240 volt service.
Electrical Requirements:
240 volt, 60 Hz, single phase, 50 or
•
40 amp., 4-wire service (line 1, line 2,
neutral, and ground)
*40 Amp Option
The heater can only be activated with the
pump on low speed. Only the spa light
can be operating at the same time without
disabling the heater. See your authorized
Vita Spa dealer to select this option.
240 Volt Installation
Permanently Connected:
The Models Envy, Grand, Joli, Cabaret,
Rendezvous, Monarque, Mystique, Prestige,
Elegant, Passion, Chateau, & Nuage come
factory set for 240 volt service.
Electrical Requirements:
240 volt, 60 Hz, single phase, 60 or
•
40 amp., 4-wire service (line 1, line 2,
neutral, and ground)
*40 Amp Option
The heater can only be activated only with
the pump on low speed. Only the spa lightl.
can be operating at the same time without
disabling the heater. See your authorized
Vita Spa dealer to select this option.
Important Safety Instructions
All electrical connections to this spa package
MUST be accomplished by a quali ed
licensed electrician in accordance with
National Electrical Code (NEC) and with state/
local electrical codes in e ect at the time of
installation.
NOTE: Prior to performing any service to
the spa equipment, turn OFF all primary
electrical power at the main circuit breaker
or disconnect panel.
Spas installed for 240 volt, 60 Hz, single
phase operation require a 4-wire, 30, 40, 50
or 60 amp., 240 volt sub-feed in non-metallic
pipe to the spa equipment compartment
(line 1, line 2, neutral and ground). A green
colored terminal (or wire connector marked
“G”, or “GR”, or “Grounding”) is provided in the
control box. To reduce the risk of electrical
shock, connect this terminal or connector to
the grounding terminal of your electrical
service or supply panel with a continuous
green insulated copper wire equivalent to
the circuit conductor supplying this equip-
ment, but no smaller than No. 12 AWG. A
second pressure wire connector is provided
on the surface of the control box for bond-
ing to local ground points. To reduce the
risk of electrical shock. this connector should
be bonded with a No. 6 AWG copper wire to
any metal ladders, water pipes, or any metal
within 5 feet of the spa.
Note: Copper wire is strongly recommended
for all electrical connections.
Caution: Risk of electrical shock.
Read and follow all instructions.