LOCATING STOVE continued…
Fig. 5a – Front View
Minimum Clearance Dimensions
from Combustible Surfaces
Fig. 5b – Side View
Minimum Clearance Dimensions
from Combustible Surfaces
13"
13"
CORNER CLEARANCES
5. Recheck c learance s f rom t he stove,
connector stove pipe, and corner clearances
using the illustrations in figures 35 and
your local building codes or fire protection
ordinances.
NOTE: Drywall faced with brick or stone must
be considered a combustible surface.
Fig. 4 – Top View
Minimum Corner Clearances
from Combustible Surfaces
CAUTION: KEEP FURNISHINGS AND OTHER
COMBUSTIBLE MATERIALS AWAY FORM
THE STOVE AND OUTSIDE MINIMUM
CLEARANCES.
6. DO NOT INSTALL THIS STOVE IN
A M O B I L E H O M E , M A N U FA C -
TURED HOME, TRAILER OR TENT
NO EXCEPTIONS! (HUD Federal
Standard: 24 CFR Ch.xx)
7. The clearances provided are minimum
dimensions determined by OMNI-Test Labo-
ratories, Inc., the manufacturer’s testing
laboratory. Installation of this stove must
comply with the latest edition of NFPA 211
for reduced clearances and/or your local build-
ing code rulings. Use whichever minimum
dimensions are LARGEST.
CAUTION: FAILURE TO FOLLOW THESE
M I N I M U M C L E A R A N C E R E Q U I R E -
ME N TS MAY R ES ULT IN A N UN SA F E
INSTALLATION AND COULD CAUSE A FIRE.
8. This stove meets U.S. Test Standard:
UL 1482-1996.
9. Always locate stove to provide a source of fresh
air into the room where the unit is installed.
Failure to do so may result in air starvation of
other fuel burning appliances and the possible
development of hazardous conditions.