Installation Guide

Page 6 / BX22EL VGZ-003 / 20120711.0
CONNECTOR PIPE INSTALLATION
NOTE: STOVE PIPE IS NOT INCLUDED.
TO PURCHASE, VISIT YOUR LOCAL HARD-
WARE, HOME OR BUILDING CENTER. USE
ROUND 6” DIA., MINIMUM 24 MSG (minimum
standard gauge) BLACK OR 26 MSG BLUE
STEEL STOVE PIPE. DO NOT USE GALVANIZED
STOVE PIPE. SEE “LOCATING STOVE” PAGES
4-5 FOR ADDITIONAL SPECIFICATIONS.
1. The crimped end of the stovepipe fits into the cast
iron damper collar. This first section must be single
walled to properly connect to the damper. Install
additional pipe and elbow(s) with the crimped end
towards the stove. This will allow any condensation
in the flue to run back into the firebox.
2. Horizontal pipe runs must slope upwards
towards the chimney at least 1/4” per foot of hori-
zontal run.
3. You must have at least 18 inches of clearance
between any horizontal piping and the ceiling.
4. The pipe cannot extend into the chimney flue (figure
3).
5. Secure pipe/elbow sections with three (3) equally
spaced sheet metal screws at each joint to make
the piping rigid.
Fig. 3 – Stovepipe/Flue Connections
CORRECT WRONG WRONG
6. It is recommended that no more than two (2)
90° bends be used in the stovepipe installa-
tion. The use of more than two 90° bends may
decrease the amount of draw and possibly
cause smoke spillage. Where possible, use only
corrugated (nonadjustable) elbows. These
provide a better seal.
7. The connector pipe must not pass through an at-
tic or roof space, closet, or any concealed space,
or floor, ceiling, wall, or combustible construction.
(See Chimney Connector Systems & Clearances,
page 15). A UL 103 HT Listed chimney must be
used from the first penetration of ceiling or wall to
the chimney cap.
Where passage through a wall or partition of com-
bustible construction is desired, the installation shall
conform to NFPA 211.
WARNING: DO NOT USE SINGLE WALL CON-
NECTOR PIPE AS A CHIMNEY - A HOUSE FIRE
COULD RESULT.