Operating instructions
heaters or furnaces.
CAUTION! Do not attach non-computer-related items, such as medical equipment, life-support
equipment, microwave ovens, or vacuum cleaners to UPS.
CAUTION! Do not plug the UPS input into its own output.
CAUTION! Condensation may occur if the UPS system is moved directly from cold to warm environment.
The UPS must be absolutely dry before being installed.
CAUTION! Place cables in such a way that no one can step on or trip over them.
CAUTION! The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be
easily accessible. The UPS power cord must be connected to an earthed mains socket outlet for safety
reasons.
CAUTION! Do not allow liquids or any foreign object to enter the UPS. Do not place beverages or any
other liquid-containing vessels on or near the unit.
CAUTION! In the event of an emergency, press the OFF button and disconnect the power cord from the
AC power supply to properly disable the UPS.
CAUTION! Do not attach a power strip or surge suppressor to the UPS.
CAUTION! If the UPS is with metal chassis, for safety purpose, grounding is a must during UPS installation
in order to reduce leakage current below 3.5mA.
Attention hazardous through electric shock. Also with disconnection of this unit from the mains,
hazardous voltage still may be accessible through supply from battery. The battery supply should be
therefore disconnected in the plus and minus pole at the quick connectors of the battery when
maintenance or service work inside the UPS is necessary.
CAUTION! Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the required precautions. Keep unauthorized personnel away from batteries.
CAUTION! When replacing the batteries, use the same number and type of batteries.
CAUTION! Avoid touching eyes while working near batteries.
CAUTION! Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or
eyes.
CAUTION! Do not disassemble the unit before contact with the qualified service center when service or
repair is required.
CAUTION! To reduce risk of injury, only use qualified batteries from qualified distributors or
manufacturers. Any unqualified batteries may cause damage and injury. Do NOT use old or overdue
batteries. Please check the battery type and date code before installation to avoid damage and injury.
CAUTION! Internal battery voltage is 12VDC. Sealed, lead-acid, 6-cell battery.
CAUTION! Do not dispose of batteries in a fire. The battery may explode. Do not open or mutilate the
battery or batteries. Released electrolyte is harmful to the skin and eyes.
CAUTION! Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
CAUTION! A battery can present a risk of electric shock and high short circuit current. The following
precaution should be observed before replacing batteries:
1) Remove watches, rings, or other metal objects.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting batteries terminal.
5. Software Download & Installation (Only for the model with
communication port)
Please follow steps below to download and install monitoring software:
1. Go to the website http://www.power-software-download.com
2. Click ViewPower software icon and then choose your required OS to download the software.
3. Follow the on-screen instructions to install the software.
4. When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.
6. Trouble Shooting
Use the table below to solve minor problems.
Problem
Possible Cause
Solutions
No words display on the
front panel even though
the mains is normal.
AC input is not connected
well.
Check if the input power cord is firmly
connected to the mains.
AC input is connected to the
UPS output.
Plug AC input power cord to AC input
correctly.
Battery backup time is
shorter than nominal
value.
Batteries are not fully
charged.
Charge the batteries at least 6 hours
and then check the capacity again.
If the problem still persists, please
consult your dealer.
Batteries defect.
Contact your dealer to replace the
batteries.
Warning or fault icon is
shown and alarm is
continuously sounding.
Fan is locked or not working.
Check fans and notify your dealer.
The UPS is overload.
Remove some loads first. Before
reconnecting devices, please verify the
total loads match the UPS capability
specified in the spec.
Low battery icon is shown
on the LCD screen.
Low battery.
Charge the UPS at least 6 hours.
7 Specifications
Model
750
1K
1.5K
2K
CAPACITY
750VA/480W
1000VA/700W
1500VA/1050W
2000VA/1400W
INPUT
Voltage
110/120 VAC or 220/230/240 VAC
Voltage Range
81-145 VAC / 162-290 VAC
OUTPUT
Voltage Regulation
+/-10%
Transfer Time
Typical 2-6 ms, 10 ms max.
Waveform
Pure Sine Wave
BATTERY
Type & Number
12V/9Ah x 1
12V/7Ah x 2
12V/9Ah x 2
12V/10Ah x 2
Charging Time
4-6 hours recover to 90% capacity
PHYSICAL
Dimension (DxWxH)
350 x 146 x 160 mm
397 x 146 x 205 mm
Net Weight (kgs)
6.8
8.96
12.18
13.7
Environment
Humidity
0-90 % RH @ 0-40°C (non-condensing)
Noise Level
Less than 45 dB
Less than 55 dB
MANAGEMENT
USB/RS-232 (option)
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and
MAC