Specifications
Model with LED Indicator & Audible Alarm 
There are three indicators (Green/Red/Yellow) in the front panel of the unit.     
Status 
LED Indicator 
Alarm 
The unit is in Line mode.   
Green LED on. 
Off 
The unit is in Line mode and 
charging battery. 
Green LED on and yellow LED 
flashes every 3 seconds. 
Battery mode 
Yellow LED flashes every 10 
seconds. 
Off 
Off-mode charging. 
Yellow LED flashes every 3 
seconds. 
Off 
Overload warning 
Yellow LED flashes every 0.5 
second 
Sounding every 0.5 
second 
Battery low warning 
Yellow LED flashes every 0.5 
second 
Sounding every second 
Output is short circuited. 
Yellow LED and red LED are 
on. 
Continuously sounding. 
The unit will shut down 
after  it’s  in  fault  mode 
for 15 seconds. 
Overload fault 
Output voltage is too low or 
too high. 
Battery bad 
Red LED is on and Green LED 
flashes every 0.5 seconds. 
Battery is overcharging. 
Red LED and Green LED are 
on. 
Battery weak. 
Red LED flashes every 0.5 
second. 
Model with LCD Display & Audible Alarm 
Status 
LCD Display 
Alarm 
Line mode 
Off 
Line mode with charging 
battery. 
  and    flashes 
Off 
Battery mode 
Off 
Off-mode charging 
  and    flashes 
Off 
Fault mode 
Fault code will be displayed. 
Output fault: F0 
Overload: F1 
Over-charging: F2 
Battery bad: F3 
High output voltage: F4 
Low output voltage: F5 
Battery weak: F6 
Continuously sounding. 
The unit will shut down 
after it’s in fault mode for 
15 seconds. 
The unit is overload. 
The mark   will flash 
every second. 
Battery weak at battery 
mode. 
The mark    will flash every 
second. 
Load level indicator:  Battery capacity indicator: 
Display 
Load Level 
Display 
Battery Capacity 
75%~100% 
battery voltage ≥ 12.5V (25V) 
50%~75% 
12.5V (25V)> battery voltage ≥ 
11.5V (23V) 
25%~50% 
11.5V (23V)> battery voltage ≥ 
11.0V (22V) 
0%~25% 
battery voltage < 11.0V (22V) 
7. Trouble Shooting 
Use the table below to solve minor problems. 
Problem 
Possible Cause 
Solutions 
Utility power is normal 
but the unit is in 
battery mode. 
AC  input  power  cord is  not 
connected well. 
Check AC input power connection. 
Input breaker is activated. 
Reset the input breaker. 
When power fails, the 
backup time is 
shorten. 
The unit is overload. 
Remove some non-critical loads. 
Battery voltage is too low. 
Charge the unit at least 8 hours. 
Battery capacity is not full 
even after charge the unit for 
at least 8 hours. 
Check the date code of the battery. If 
the batteries are too old, replace the 
batteries. 
Nothing display on the 
front panel when the 
utility power is 
normal. 
The unit is not turned on. 
Press  power  switch  to  turn  on  the 
unit. 
Battery is not connected well. 
Check the external battery cable and 
terminal.  Make  sure  all  the battery 
connections to the unit are all correct. 
Battery defect.   
Replace the batteries. 
Battery voltage is too low. 
Charge the unit at least 8 hours. 
The unit is in fault and 
restart circularly. 
The unit is overload. 
Verify that the load matches the 
capability specified in the 
specification. 
Output is short circuited. 
Check  the  loads and  remove  loads 
which cause short circuit. 
If there is any abnormal situations occur, which doesn't list above, please call the service 
people immediately for professional examine. 