User manual

21
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable
(default)
Bypass enable
25
Record Fault code
Record enable
Record disable (default)
26
Bulk charging voltage
(C.V voltage)
1KVA default setting: 14.1V
2K/3KVA default setting: 28.2V
4K/5KVA default setting: 56.4V
If self-defined is selected in program 5, this program can
be set up. Setting range is from 12.0V to 14.6V for 1K
model, 24.0V to 29.2V for 2K/3K model and 48.0V to 58.4V
for 4K/5K model. Increment of each click is 0.1V.
27
Floating charging voltage
1KVA default setting: 13.5V
2K/3KVA default setting: 27.0V
4K/5KVA default setting: 54.0V
If self-defined is selected in program 5, this program can
be set up. Setting range is from 12.0V to 14.6V for 1K
model, 24.0V to 29.2V for 2K/3K model and 48.0V to 58.4V
for 4K/5K model. Increment of each click is 0.1V.