Installation Guide

Installation Instructions
6113/6113DS Electric Strike
®
Figure 1
DC input is
nonpolarized.
NOTE
!
J1
J2
P2
Switches shown with tripper
depressed, strike lip closed and locked
(switches and tripper on 6113DS only)
P1
P1 J1A P1A
SO-12 or SO-24
12 VDC
or
24 VDC
12 VAC SO-12 12 VDC
or
24 VAC SO-24 24 VDC
{
{
J2
Fail safe (FS)
J2
Fail secure (FSE)
S1
S2
1
2
3
4
5
6
S1
S2
1
2
3
4
5
6
Wiring
for DC
supply
Wiring
for AC
supply
931220_00(9) Copyright © 2005 Ingersoll-Rand. All rights reserved.
Solenoid
89/336/EEC
Standard: 5 A, 30 VDC
Gold: 0.25 A, 30 VDC
SWITCH RATINGS
}
P2
Red (C)
Blue
Yellow
White (C)
Gray
Violet
}
S1
(monitors
tripper)
S2
(monitors
strike lip)
Use crimp
connectors to
splice field wiring
to P1 leads
Yellow solenoid wires = 12 VDC, 0.57 A
Black solenoid wires = 24 VDC, 0.29 A
(also shown on strike label)
SOLENOID POWER REQUIREMENTS
4. Test strike: Apply solenoid power. Fail secure (FSE) lip unlocks.
Fail safe (FS) lip locks. Figure 1 shows status of switches.
5. Install strike with two #12-24 screws. Make sure clearance
between latch bolt and strike lip is 1/32 (Figure 2).
6. If latch bolt does not extend far enough to actuate tripper,
install extension (Figure 3). (Tripper on 6113DS only.)
7. Test door: With strike unlocked, door opens with latch bolt
extended. When door closes, latch bolt rides over strike lip.
Note: Check with factory for retrofit applications.
1. For lock or device preparation, see their directions.
Also see application schedule on other side.
2. Prepare frame for strike (see other side).
3. Wire strike (Figure 1). (Switches on 6113DS only.)
Single Door Rim Application
Use crimp connectors to
splice field wiring to P2
leads; insulate unused leads
Tripper
Figure 3
Extension
931220-00
Figure 2
Top view;
faceplate not
shown for clarity
1/32
Latch bolt
Strike lip