Air curtains control
• The motor is controlled by applying voltages in the range 0-10VDC to terminals Ai and G
• The motor will not start when a voltage of 0-1VDC is applied to terminals Ai and G
• The motor speed is controlled by changing the voltage supply to the terminals Ai and G in the range 1-10VDC. The value of the given voltage in a linear manner influences the motor speed in the
range from 10-100% of its full efficiency.
• The electric heating coils should only be turned ON when the motor is running at least 45% of its full capacity. Starting electric heating coils when the motor is switched OFF can be dangerous and
can lead to damage to the device.
• Electric heating coils are divided into two independent sections controlled by applying 240VAC to terminals 2 and 3 on the terminals of electric curtains
EN
IMPORTANT!
• It is recommended to connect wires to the terminal strip with previously clamped appropriate clip ends.
• Make sure that the space around the place where the air is sucked in by the curtains, as well as around the exhaust grid, is free of any structural elements of the building, which might hamper the
flow of air (e.g. suspended ceilings, covering development, ventilating ducts etc.).