Installation guide

21
RE Sp
Reset humidity setpoint
Default value = 20% RH
The RH setpoint will be reset from the user setpoint
to this value when the RH LT outside air
temperature value is reached.
Only valid if an outdoor air sensor is connected at
the thermostat or a network value is transmitted to
the thermostat. See RH LT & RE HT.
From 10% RH up to 90% RH
RH cal
Humidity sensor calibration
Default value = 0 %RH
Offset that can be added/subtracted to actual
displayed humidity by ± 15.0 %RH.
This calibration applies to the internal humidity
sensor if no remote humidity sensor is connected.
This calibration applies to the remote humidity
sensor when one is connected.
From –15% RH up to 15% RH
Display
HL
Display the high limit sensor value Used as diagnostic / service help to troubleshoot
and diagnose sensor / humidifier operation
Note:
When the outside air sensor is not connected or is shorted, the thermostat bypasses:
The heating lockout
The cooling lockout
The dehumidification lockout
The humidity setpoint reset