INSTALLATION INSTRUCTION
100W/150W Enclosed Electronic Transformer
EN-12100-RB-AR, EN-12150-RB-AR
CAUTION – TO REDUCE RISK OF FIRE AND ELECTRICAL SHOCK
Always turn o power at main switch prior to installation.
Intended for installation by a qualied electrician.
System is intended for installation in accordance with National Electric Code, and local regulations.
Consult with local inspector to assure compliance.
EN-12100-RB-AR EN-12150-RB-AR
MAX LOAD 100W 150W
MIN LOAD 35W 50W
INPUT VOLTAGE 120V 120V
INPUT CURRENT 0.83A 1.3A
OUTPUT VOLTAGE 11.6V 11.6V
FEATURES
Radio disturbance suppression.
Electronic short circuit protection with auto reset.
Overload protection with auto reset.
Soft start delay to preserve lamp life, for use with tungsten lament lamps.
Dimmable with electronic dimmer switches.
INSTALLATION:
1. Use #14 AWG (minimum) wire for output wire.
2. Transformers must be installed away from heat sources and accessible for service.
3. Dimmer switches install on the primary side.
4. Note: Enclosed transformer is UL listed. The transformer box has a separate line volt, and low volt wiring compartments. Trade
size knock out are provided on both compartments. Connect building wires to like color transformer wires with wire nuts.
Building ground wire may be green or un-insulated, and attaches to green wire on transformer box.
5. Connect out put wires from transformer to xture wires with wire nuts. Where multiple xtures are involved several xtures
wires can be joined by use of the same wire nut. Wires to xtures may be chain wired or “ home run” wired back to the trans-
former. High frequency output is only readable with a true RMS meter, with sucient range capability.
6. Low volt wiring concealed in walls and ceilings requires enclosed and clamped connections.
MAXIMUM LENGTH / VOLTAGE DROP GUIDELINE
WIRE SIZE LOAD
35 W 50 W 60 W 100 W 150 W
14 GAUGE 21 FT 19 FT 17 FT 15 14
12 GAUGE 28 FT 25 FT 22 FT 20 18