Installation Sheet

4/4
INSTRUCTIONS: Line Volt Flexrail1
Safety Instructions:
A qualified electrician must install system only. System is intended for installation in
accordance with National Electric Code, local and Federal code specifications.
To reduce the risk of fire, electrical shock and injuries to persons:
1. Read all instructions.
2. Turn off power at main switch before installing or modifying the system.
3. Do not install within six inches of any curtain or combustible materials.
4. Do not install less than 5 feet above a floor.
5. Do not install in damp or wet locations.
6. Do not install concealed, or extended through building walls.
7. Do not attempt to energize anything other than a track light fixture.
8. Do not load rail to more than 20 amps per circuit.
Overview:
Line volt bendable rail (24” min radius). May be hand bent, optional bending tool for large jobs.
Mounting options for flat, sloped or T-bar ceilings.
Allows custom length ceiling suspension.
Available in 4 & 8 ft lengths and may be joined to form longer runs.
Use rope, chalk or string on floor level, or a scale drawing with string to estimate rail needs.
Accepts Line volt and low volt fixtures, line volt pendants, and quick connect transformers used
with QC series pendants or fixtures.
Powers from a standard ceiling fixture box.
A = Power feed
B = Standoff
C = Quick Connect transformer with low volt pendant
D = “I” Connector ( joins two rail sections & supports)
E = Line volt fixture
F = Quick Connect transformer with low volt fixture
G = Line Volt pendant
H = Low volt fixture