User manual

92 UA964801 - User manual User manual - UA964801 93
11.8 Graphic
Parameters to congure the trend and bar graph management.
 Graphic type
Selects the type of graph to be visualized on the relevant page.
Trend (
Default
)
Bar graph
 Lower limit
Trend or bar graph lower limit.
-32767 to +32767 [Digit
2
],
Default
: 0.
 Upper limit
Trend or bar graph upper limit.
-32767 to +32767 [Digit
2
],
Default
: 1000.
 Trend time
Selects the trend sampling time.
1 to 3600 seconds,
Default
: 60s.
 Data logger
Enables the over time registration of the process in eeprom
The sampling time is equal to the trend upgrading time.
Disabled (
Default
)
Enabled
11.9 Analogue output in mA
Parameters to congure the analogue output in mA
 Retransmission
Enables analogue output
Disabled (
Default
)
Process
Alarm 1
Alarm 2
Remote control
 Signal type
Selects the signal for the analogue output in mA
0 to 20 mA
4 to 20 mA (
Default
)
 Lower limit
Analogue output mA lower limit range
-32767 to +32767 [Digit
2
] (degrees.tenths for temperature sensors),
Default
: 0
 Upper limit
Analogue output mA upper limit range
-32767 to +32767 [Digit
2
] (degrees.tenths for temperature sensors)
Default
: 1000
 Error value
Selects the value of the analogue output in mA in case of error
0 mA (
Default
)
4 mA
20 mA
11.10 Analogue output in Volt
Parameters to congure the analogue output in Volt
 Retransmission
Enables analogue output
Disabled (
Default
)
Process
Alarm 1
Alarm 2
Remote control