Press Eect Do
FNC
for  sec.
Display  shows 0000
with the st digit
ashing, while display
 shows
pass
or
Change the ashing
digit and move to the
next one using the
SET
key.
Enter password
9999
SET
to conrm
Instrument loads
default settings
Turn o and restart
the instrument
. LATCH ON Functions
For use with input
P o t .1
(potentiometer 6K) and
Po t.2
(po-
tentiometer 150K) and with linear input (0…10V, 0...40mV,
0/420mA), it is possible to associate start value of the scale
(parameter 6
Lo .L.i .
) to the minimum position of the sensor
and value of the scale end (parameter 7
u p. L.i .
) to the maxi-
mum position of the sensor (parameter 8
La t c.
congured as
std.
).
It is also possible to x the point in which the controller will
display 0 (however keeping the scale range between
Lo .L.i .
and
u p. L.i .
) using the “virtual zero” option by setting
u.0st.
or
u.0in.
in parameter 8
La t c.
If you set
u.0in.
the virtual zero
will reset after each activation of the tool; if you set
u.0st.
the
virtual zero remains xed once tuned.
To use the LATCH ON function, congure according to requi-
red operation the parameter
La t c.
The tuning procedure starts by exiting the conguration after changing