User manual
20 UR3274U - User manual
For the calibration procedure refer to the following table:
Press E e c t Do
FNC
Exit parameters
con guration. Display
shows the writing
La t c.
Place the sensor on the
minimum functioning
value (associated with
Lo .L.i .
)
Set the value to
minimum.
The display shows
Lo w
Place the sensor on the
maximum functioning
position
(associated with
u p. L.i .
)
Set the value to
maximum.
The display shows
Hi G t
To exit standard
procedure press
FNC
.
For “virtual zero”
settings place the sensor
on zero point.
SET
Set the virtual zero
value. The display shows
ui rt .
NB: for selection
of
u.0in.
the procedure
on point should
be followed at each
re-activation.
To exit the procedure
press
FNC
.
Max
Min Zero
the parameter.