d. t.L.M.
(Double Timer Loop Minutes) time-basis in minutes
(hh.mm)
To start/stop the Timer, press
FNC
for 1 “.
During the counting, Led
R
is On (xed for Timer1, ashing
for Timer 2) and display2 shows decrementing time. Start is
always made on Timer 1.
Start/Stop of Timer is possibile also by digital input, selecting
t.1.s.s.
on parameter 50
d Gt.i .
. Relating Timers to Alarms
It is possible to associate the alarms (relay or SSR outputs) to
the timers by parameters 23
a L. 1
and 31
a L. 2.
The table be-
low is showing the combined operation of alarms and Timers.
Selection
par. or
Description
t .1 . s . a .
Timer Start Alarm
Alarm active as long as Timer is in
Start mode (Timer active)
t .1 . E . a .
Timer End Alarm
Alarm active at elapsing of Timer until
any key is pressed. Option not available
for Dual sequential Timer and Dual
Timer Loop.
t.1.W. a .
Timer Warning
Expiring
Alarm active for the last ” of Timer
t.2. s . a .
Timer Start Alarm
Alarm active as long as Timer is in
Start mode (Timer active)
t.2.e.a.
Timer End Alarm
Alarm active at elapsing of Timer until
any key is pressed. Option not available
for Dual sequential Timer and Dual
Timer Loop.