Visualized Setpoint  (decimal as
display)
R/W EEPROM

Visualized Setpoint  (decimal as
display)
R/W EEPROM

Visualized Setpoint  (decimal as
display)
R/W EEPROM

Visualized Setpoint  (decimal as
display)
R/W EEPROM

Visualized Alarm  (decimal as
display)
R/W EEPROM

Visualized Alarm  (decimal as
display)
R/W EEPROM

Setpoint gradient (decimal as
display)
RO EEPROM

Heating output percentage
(-)
RO
 Heating output percentage (-) RO

Cooling output percentage
(-)
RO
 Cooling output percentage (-) RO
 Parameter  R/W EEPROM
... ... ... ...
 Parameter  R/W EEPROM

Disabling serial control of
machine
**
WO
 First word display (ASCII) R/W
*
If value is 0, the control is disabled. If dierent from 0, it is the max. time
which can elapse between two pollings before the controller goes o-
line. If it goes o-line, the controller returns to Stop mode, the control
output is disabled but the alarms are active.
**
By writing 1 on this word, the eects of the writing are cancelled on all
the Modbus addresses from 3001 to 3022. Control therefore returns to
the controller.