User manual
UR3274U - User manual 39
d. p.
Decimal Point
select number of displayed decimal points.
0
> Default
0.0
0.00
0.000
Lo .L. s .
Lower Limit Setpoint
lower limit setpoint.
-…+ [digit
] (degrees.tenths for temperature
sensors) Default: 0.
U P. L. S.
Upper Limit Setpoint
upper limit setpoint.
-…+ [digit
] (degrees.tenths for temperature
sensors) Default: 1750.
Lo .L.i .
Lower Linear Input
lower range limit AN1 only for linear input.
-…+ [digit
] Default: 0.
u p. L.i .
Upper Linear Input
upper range limit AN1 only for linear input.
-…+ [digit
] Default: 1000.
La t c.
Latch On Function
automatic setting of limits for Linear input.
di s .
Disabled > Default
std.
Standard
v.0.st.
Virtual Zero Stored
v.0.in.
Virtual Zero Initialized