User manual
UR3274U - User manual 41
c. HY.
Command Hysteresis
hysteresis in ON/OFF or dead band in P.I.D.
-…+ [digit
], (degrees.tenths for temperature
sensors) > Default: 0.0
c. d e.
Command Delay
(only in ON/OFF functioning).(In case of servo valve it also
functions in PID and represents the delay between the
opening and closure of the two contacts).
-…+ seconds, tenths of second in case of servo valve.
Negative: delay in switching o phase.
Positive: delay in activation phase.
Default: 0.
c. s. p.
Command Setpoint Protection
allow/deny modications of command setpoint by frontal
keyboard.
free
> Default
Lo ck.
Locked
p. b.
Proportional Band
process inertia in units (°C if temperature).
on/o if
t.i .
equal to . > Default
- [digit
], (degrees for temperature sensors).
t.i .
Integral Time
process inertia in seconds
.-. sec. (0 excludes integral) > Default: 0.
t.d.
Derivative Time
normally ¼ of integral time.
.-. sec. (0 excludes derivative) > Default: 0.
The display of decimal point depends on the setting of parameter
sen.
and the parameter
d. p.