User manual

UR3274U - User manual 45

a .2. re.
Alarm  Reset
type of Reset for contact of alarm 2.
a. re.
Automatic Reset > Default
m. re.
Manual Reset
m. re.s .
Manual Reset Stored

a .2. s . e .
Alarm  State Error
state of contact for alarm 2 output in case of error.
n.o.
> Default
n. c.

a.2.Ld.
Alarm  Led
state of OUT2 led corresponding to relative contact.
n.o.
n. c.
> Default

a.2.HY.
Alarm  Hysteresis
-+ [digit
], (degrees.tenths for temperature
sensors). > Default: 0.

a .2. d e.
Alarm  Delay
-+ Sec. > Default: 0.
Negative: delay in alarm output phase.
Positive: delay in alarm entry phase.

a .2. s . p.
Alarm  Setpoint Protection
Alarm 2 set protection.
Does not allow operator to change setpoint value.
free
> Default
Lo ck.
Locked
Hi d e
Locked and hidden

co o . f.
Cooling Fluid
select type of cooling uid for Heating/Cooling PID