User manual
56 UR3274U - User manual
O
On On
Hysteresis
parameter
> 0
Pv.
Alarm Spv
Command Spv
Time
Alarm output
Lower deviation alarm value
of alarm setpoint less than
“0” and hysteresis value
greater than “0” (Par. 28
a .1 . H y . > 0).
NB: a) The example refers to alarm 1; function can also be
enabled for alarm 2 on model that include it.
b) With hysteresis value less than “0” (
a .1 . H y . < 0) the
dotted line moves under alarm setpoint.
Table of Anomaly Signals
If installation malfunctions, controller will switch o regula-
tion output and will report the anomaly. For example, control-
ler will report failure of a connected thermocouple visualizing
e -05 ashing on display for other signals, see table below.
Cause What to do
E - 01
sYs. e.
Error in E²PROM cell
programming
Call Assistance
E-02
sYs. e.
Cold junction sensor
fault or room tempera-
ture outside of allowed
limits.
Call Assistance
E-04
sYs. e.
Incorrect con guration
data. Possible loss of
calibration values.
Check if the con gu-
ration parameters are
correct.
E-05
prb.
Thermocouple open or
temperature outside of
limits.
Check the connection
with the sensors and
their integrity.